Assessment Year | 2018 |
---|---|
Principal Product | Potato and Corn Chips |
NAICS | 311919: Other Snack Food Manufacturing |
SIC | 2096: Potato Chips, Corn Chips, and Similar Snacks |
Sales Range | greater than $500 M |
# of Employees | 350 |
Plant Area |
300,000
ft2
|
Annual Production | 100,000,000
lb
|
Production Hrs. Annual | 7,488
hrs
|
Location (State) | Washington |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $688,235 | 14,735,370 |
kWh
|
$0.047 | |
Electricity Demand | $160,520 | 27,038 |
kW-mo/yr
|
$5.94 | |
Electricity Fees | $23,740 | - |
|
- | |
Natural Gas | $1,182,798 | 315,758 |
MMBtu
|
$3.75 | |
Waste Disposal Costs | |||||
Water Usage | $384,872 | 159,192 |
Tgal
|
$2.42 | |
Solid Waste (non-haz) | $348,130 | 2,248,817 |
lb
|
$0.15 | |
TOTAL YEARLY COSTS | $2,788,295 | ||||
RECOMMENDED SAVINGS* | $331,648 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $225,013 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Solid Waste (non-haz) Savings |
---|---|---|---|---|---|---|---|---|
01 | 3.6193: Install equipment (eg compactor) to reduce disposal costs | $200,991 | $689,600 |
$(-41,679.0)
(-848,854)
kWh
|
$(-7,733.0)
-
kW-mo/yr
|
- |
$250,403
-
lb
|
|
02 | 2.1224: Replace boiler | $56,825 | $365,566 |
$804
16,378
kWh
|
- |
$56,021
-
MMBtu
|
- | |
03 | 2.2444: Use hot process fluids to preheat incoming process fluids | $33,804 | $25,271 | - | - |
$33,804
-
MMBtu
|
- | |
04 | 2.2414: Use waste heat from hot flue gases to preheat | $16,006 | $21,662 | - | - |
$16,006
-
MMBtu
|
- | |
05 | 2.2511: Insulate bare equipment | $17,619 | $17,511 | - | - |
$17,619
-
MMBtu
|
- | |
06 | 2.5196: Use small number of high output units instead of many small inefficient units | $6,403 | $30,000 |
$5,493
111,874
kWh
|
$910
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $331,648 | $1,149,610 |
$(-35,382.0)
(-720,602)
kWh
|
$(-6,823.0)
-
kW-mo/yr
|
$123,450
-
MMBtu
|
$250,403
-
lb
|
||
TOTAL IMPLEMENTED | $225,013 | $737,111 |
$(-36,186.0)
(-736,980)
kWh
|
$(-6,823.0)
-
kW-mo/yr
|
$17,619
-
MMBtu
|
$250,403
-
lb
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Solid Waste (non-haz) Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs