Assessment Year | 1989 |
---|---|
Principal Product | MECH.SPRINGS,WIRES FORMS |
NAICS |
n/a
|
SIC | 3495: Wire Springs |
Sales Range | $5 M to 10M |
# of Employees | 100 |
Plant Area |
n/a
|
Annual Production | 0
units
|
Production Hrs. Annual | 5,000
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $68,464 | 974,209 |
kWh
|
$0.070 |
Natural Gas | $23,699 | 6,593 |
MMBtu
|
$3.59 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $13,701 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $4,733 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.7261: Install timers and/or thermostats | $5,126 | $1,300 | - |
$5,126
-
MMBtu
|
- | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,780 | $5,000 |
$2,780
39,566
kWh
|
- | - | |
03 | 2.2414: Use waste heat from hot flue gases to preheat | $1,616 | $7,000 | - |
$1,616
-
MMBtu
|
- | |
04 | 2.8113: Purchase gas directly from a contract gas supplier | $1,353 | - | - |
$1,353
-
MMBtu
|
- | |
05 | 2.4312: Improve lubrication practices | $1,174 | - |
$1,174
16,706
kWh
|
- | - | |
06 | 2.3191: Use demand controller or load shedder | $1,052 | - |
$1,152
-
kWh
|
- | $(-100.0) | |
07 | 2.4221: Install compressor air intakes in coolest locations | $600 | $1,000 |
$600
8,499
kWh
|
- | - | |
TOTAL RECOMMENDED | $13,701 | $14,300 |
$5,706
64,771
kWh
|
$8,095
-
MMBtu
|
$(-100.0) | ||
TOTAL IMPLEMENTED | $4,733 | $6,000 |
$3,380
48,065
kWh
|
$1,353
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs