Assessment Year | 1988 |
---|---|
Principal Product | MILK, ICE CREAM, CHEESE |
NAICS |
n/a
|
SIC | 2026: Fluid Milk |
Sales Range | $10 M to 50M |
# of Employees | 100 |
Plant Area |
n/a
|
Annual Production | 0
units
|
Production Hrs. Annual | 5,500
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $472,194 | 6,735,932 |
kWh
|
$0.070 |
Natural Gas | $97,219 | 29,664 |
MMBtu
|
$3.28 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $38,247 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $21,956 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.4312: Improve lubrication practices | $5,607 | - |
$5,607
80,012
kWh
|
- | - | |
02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,804 | - |
$2,804
39,859
kWh
|
- | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $687 | $417 |
$687
9,672
kWh
|
- | - | |
04 | 2.3132: Recharge batteries on during off-peak demand periods | $894 | $500 |
$894
-
kWh
|
- | - | |
05 | 2.7226: Use computer programs to optimize hvac performance | $7,516 | $8,000 |
$7,516
107,268
kWh
|
- | - | |
06 | 2.2511: Insulate bare equipment | $608 | $360 |
$608
8,792
kWh
|
- | - | |
07 | 2.4221: Install compressor air intakes in coolest locations | $1,534 | $1,000 |
$1,534
21,981
kWh
|
- | - | |
08 | 2.2621: Modify refrigeration system to operate at a lower pressure | $14,600 | - |
$14,600
208,382
kWh
|
- | - | |
09 | 2.7447: Install vinyl strip / high speed / air curtain doors | $2,248 | $700 | - |
$2,248
-
MMBtu
|
- | |
10 | 2.1233: Analyze flue gas for proper air/fuel ratio | $1,749 | $250 | - |
$1,849
-
MMBtu
|
$(-100.0) | |
TOTAL RECOMMENDED | $38,247 | $11,227 |
$34,250
475,966
kWh
|
$4,097
-
MMBtu
|
$(-100.0) | ||
TOTAL IMPLEMENTED | $21,956 | $250 |
$20,207
288,394
kWh
|
$1,849
-
MMBtu
|
$(-100.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs