| Assessment Year | 1988 |
|---|---|
| Principal Product | COUPLERS, WRENCHES, ETC. |
| NAICS |
n/a
|
| SIC | 3568: Mechanical Power Transmission Equipment, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 95 |
| Plant Area |
n/a
|
| Annual Production | 0
units
|
| Production Hrs. Annual | 2,125
hrs
|
| Location (State) | Wisconsin |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $74,864 | 879,836 |
kWh
|
$0.085 |
| Natural Gas | $35,050 | 7,333 |
MMBtu
|
$4.78 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $18,791 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $3,061 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4312: Improve lubrication practices | $230 | - |
$230
2,638
kWh
|
- | - | |
| 02 | 2.4221: Install compressor air intakes in coolest locations | $336 | $956 |
$336
4,103
kWh
|
- | - | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,124 | $2,325 |
$2,124
24,912
kWh
|
- | - | |
| 04 | 2.7447: Install vinyl strip / high speed / air curtain doors | $1,290 | $1,500 | - |
$1,290
-
MMBtu
|
- | |
| 05 | 2.8113: Purchase gas directly from a contract gas supplier | $10,059 | - | - |
$10,059
-
MMBtu
|
- | |
| 06 | 2.1233: Analyze flue gas for proper air/fuel ratio | $371 | $500 | - |
$471
-
MMBtu
|
$(-100.0) | |
| 07 | 2.7226: Use computer programs to optimize hvac performance | $4,381 | $3,000 |
$4,381
51,583
kWh
|
- | - | |
| TOTAL RECOMMENDED | $18,791 | $8,281 |
$7,071
83,236
kWh
|
$11,820
-
MMBtu
|
$(-100.0) | ||
| TOTAL IMPLEMENTED | $3,061 | $3,781 |
$2,690
31,653
kWh
|
$471
-
MMBtu
|
$(-100.0) | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs