| Assessment Year | 2025 |
|---|---|
| Principal Product | Structural Steel Fabrication |
| NAICS | 332312: Fabricated Structural Metal Manufacturing |
| SIC | 3599: Industrial and Commercial Machinery and Equipment, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 124 |
| Plant Area |
187,600
ft2
|
| Annual Production | 11,712
ton
|
| Production Hrs. Annual | 6,048
hrs
|
| Location (State) | Washington |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $181,705 | 1,739,600 |
kWh
|
$0.10 |
| Electricity Demand | $32,218 | 5,781 |
kW-mo/yr
|
$5.57 |
| Electricity Fees | $26,998 | - |
|
- |
| Natural Gas | $60,273 | 5,917 |
MMBtu
|
$10.19 |
| LPG | $26,272 | 921 |
MMBtu
|
$28.53 |
| Other Gas | $5,222 | 1 |
MMBtu
|
$5,222.00 |
| TOTAL YEARLY COSTS | $332,688 | |||
| RECOMMENDED SAVINGS* | $169,064 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | LPG Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.4221: Install compressor air intakes in coolest locations | $24,319 | $2,741 |
$24,226
242,261
kWh
|
$93
-
kW-mo/yr
|
- | - | |
| 02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $24,637 | $15,000 |
$22,254
212,958
kWh
|
$2,383
-
kW-mo/yr
|
- | - | |
| 03 | 2.9114: Use solar heat to make electricty | $60,995 | $262,084 |
$55,177
528,014
kWh
|
$5,818
-
kW-mo/yr
|
- | - | |
| 04 | 2.7447: Install vinyl strip / high speed / air curtain doors | $16,531 | $210,600 | - | - |
$16,531
-
MMBtu
|
- | |
| 05 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $9,594 | $149,864 | - | - | - |
$9,594
-
MMBtu
|
|
| 06 | 2.4321: Upgrade obsolete equipment | $32,988 | $55,500 |
$32,700
312,984
kWh
|
$288
-
kW-mo/yr
|
- | - | |
| TOTAL RECOMMENDED | $169,064 | $695,789 |
$134,357
1,296,217
kWh
|
$8,582
-
kW-mo/yr
|
$16,531
-
MMBtu
|
$9,594
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | LPG Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs