Assessment Year | 2010 |
---|---|
Principal Product | Soft Drinks |
NAICS | 312111: Soft Drink Manufacturing |
SIC | 2086: Bottled and Canned Soft Drinks and Carbonated Waters |
Sales Range | $100 M to 500M |
# of Employees | 300 |
Plant Area |
200,000
ft2
|
Annual Production | 15,000,000
pieces
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Michigan |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $373,353 | 7,772,222 |
kWh
|
$0.048 |
Electricity Demand | $265,962 | 17,938 |
kW-mo/yr
|
$14.83 |
Natural Gas | $561,274 | 61,645 |
MMBtu
|
$9.10 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $200,760 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $128,394 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $76,860 | $90,000 |
$48,208
1,003,492
kWh
|
$28,652
-
kW-mo/yr
|
- | |
02 | 2.7135: Install occupancy sensors | $17,172 | $8,188 |
$17,172
357,448
kWh
|
- | - | |
03 | 2.4323: Use optimum size and capacity equipment | $11,691 | $7,980 |
$11,691
243,360
kWh
|
- | - | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $6,537 | $200 |
$4,102
85,387
kWh
|
$2,435
-
kW-mo/yr
|
- | |
05 | 2.6211: Conserve energy by efficient use of vending machines | $2,121 | $10 |
$519
10,800
kWh
|
$1,602
-
kW-mo/yr
|
- | |
06 | 2.4221: Install compressor air intakes in coolest locations | $1,990 | $1,000 |
$1,248
25,985
kWh
|
$742
-
kW-mo/yr
|
- | |
07 | 2.2437: Recover waste heat from equipment | $33,206 | $1,000 |
$11,500
239,381
kWh
|
$6,837
-
kW-mo/yr
|
$14,869
-
MMBtu
|
|
08 | 2.7447: Install vinyl strip / high speed / air curtain doors | $30,358 | $27,940 | - | - |
$30,358
-
MMBtu
|
|
09 | 2.7243: Improve air circulation with destratification fans / other methods | $19,669 | $15,750 | - | - |
$19,669
-
MMBtu
|
|
10 | 2.7494: Install storm windows and doors | $1,156 | $9,300 | - | - |
$1,156
-
MMBtu
|
|
TOTAL RECOMMENDED | $200,760 | $161,368 |
$94,440
1,965,853
kWh
|
$40,268
-
kW-mo/yr
|
$66,052
-
MMBtu
|
||
TOTAL IMPLEMENTED | $128,394 | $108,488 |
$76,880
1,600,321
kWh
|
$35,489
-
kW-mo/yr
|
$16,025
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs