Assessment Year | 2009 |
---|---|
Principal Product | release agents and specialty lubricants |
NAICS | 325998: All Other Miscellaneous Chemical Product and Preparation Manufacturing |
SIC | 2899: Chemicals and Chemical Preparations, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 160 |
Plant Area |
150,000
ft2
|
Annual Production | 9,000
Tgal
|
Production Hrs. Annual | 2,210
hrs
|
Location (State) | Michigan |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $193,394 | 2,908,235 |
kWh
|
$0.066 |
Electricity Demand | $69,092 | 4,846 |
kW-mo/yr
|
$14.26 |
Natural Gas | $326,343 | 36,051 |
MMBtu
|
$9.05 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $78,020 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $60,686 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7314: Reduce ventilation air | $20,146 | $500 | - | - |
$20,146
-
MMBtu
|
|
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $17,026 | $50,000 |
$7,614
114,427
kWh
|
$9,412
-
kW-mo/yr
|
- | |
03 | 2.7263: Lower compressor pressure through a/c system modification | $13,963 | $400 |
$11,831
27,538
kWh
|
$2,132
-
kW-mo/yr
|
- | |
04 | 2.2449: Recover heat from exhausted steam, hot air or hot water | $11,980 | $9,000 | - | - |
$11,980
-
MMBtu
|
|
05 | 2.7494: Install storm windows and doors | $6,298 | $24,510 | - | - |
$6,298
-
MMBtu
|
|
06 | 2.7241: Install outside air damper / economizer on hvac unit | $2,724 | $7,574 | - | - |
$2,724
-
MMBtu
|
|
07 | 2.4221: Install compressor air intakes in coolest locations | $2,630 | $5,000 |
$790
11,884
kWh
|
$1,840
-
kW-mo/yr
|
- | |
08 | 2.2437: Recover waste heat from equipment | $1,620 | $10,000 | - | - |
$1,620
-
MMBtu
|
|
09 | 2.7135: Install occupancy sensors | $1,161 | $30,000 |
$1,161
17,464
kWh
|
- | - | |
10 | 2.2136: Install / repair insulation on steam lines | $472 | $10,000 | - | - |
$472
-
MMBtu
|
|
TOTAL RECOMMENDED | $78,020 | $146,984 |
$21,396
171,313
kWh
|
$13,384
-
kW-mo/yr
|
$43,240
-
MMBtu
|
||
TOTAL IMPLEMENTED | $60,686 | $125,410 |
$20,606
159,429
kWh
|
$11,544
-
kW-mo/yr
|
$28,536
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs