| Assessment Year | 2015 |
|---|---|
| Principal Product | Food Packaging Plastics |
| NAICS | 326199: All Other Plastics Product Manufacturing |
| SIC | 3089: Plastics Products, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 110 |
| Plant Area |
250,000
ft2
|
| Annual Production | 22,300,000
lb
|
| Production Hrs. Annual | 8,400
hrs
|
| Location (State) | Kentucky |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,033,869 | 22,300,472 |
kWh
|
$0.046 |
| Electricity Demand | $231,587 | 36,934 |
kW-mo/yr
|
$6.27 |
| Electricity Fees | $176,232 | - |
|
- |
| Natural Gas | $72,493 | 8,979 |
MMBtu
|
$8.07 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $98,726 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $25,186 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $49,404 | $93,500 |
$40,814
887,264
kWh
|
$8,590
-
kW-mo/yr
|
- | |
| 02 | 2.7134: Use photocell controls | $5,777 | $34,255 |
$5,777
125,580
kWh
|
- | - | |
| 03 | 2.7124: Make a practice of turning off lights when not needed | $453 | $405 |
$453
9,855
kWh
|
- | - | |
| 04 | 2.4221: Install compressor air intakes in coolest locations | $2,355 | $2,550 |
$1,971
42,480
kWh
|
$384
-
kW-mo/yr
|
- | |
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $11,588 | $1,750 |
$9,699
210,840
kWh
|
$1,889
-
kW-mo/yr
|
- | |
| 06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,819 | - |
$1,819
39,545
kWh
|
- | - | |
| 07 | 2.4152: Use only certified motor repair shops | $6,448 | $6,381 |
$6,448
140,180
kWh
|
- | - | |
| 08 | 2.2442: Preheat combustion air with waste heat | $6,299 | $2,520 | - | - |
$6,299
-
MMBtu
|
|
| 09 | 2.2511: Insulate bare equipment | $2,405 | $810 | - | - |
$2,405
-
MMBtu
|
|
| 10 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,473 | - |
$2,473
53,760
kWh
|
- | - | |
| 11 | 2.2614: Use cooling tower or economizer to replace chiller cooling | $9,705 | $17,000 |
$9,705
210,980
kWh
|
- | - | |
| TOTAL RECOMMENDED | $98,726 | $159,171 |
$79,159
1,720,484
kWh
|
$10,863
-
kW-mo/yr
|
$8,704
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $25,186 | $9,346 |
$20,892
454,180
kWh
|
$1,889
-
kW-mo/yr
|
$2,405
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs