Assessment Year | 2025 |
---|---|
Principal Product | Optical Componenents |
NAICS | 333314: Optical Instrument and Lens Manufacturing |
SIC | 3827: Optical Instruments and Lenses |
Sales Range | $10 M to 50M |
# of Employees | 120 |
Plant Area |
41,000
ft2
|
Annual Production | 1,000,000
units
|
Production Hrs. Annual | 4,000
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $232,673 | 2,669,047 |
kWh
|
$0.087 |
Electricity Demand | $66,485 | 12,548 |
kW-mo/yr
|
$5.30 |
Electricity Fees | $32,939 | - |
|
- |
TOTAL YEARLY COSTS | $332,097 | |||
RECOMMENDED SAVINGS* | $179,034 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.9114: Use solar heat to make electricty | $59,131 | $322,608 |
$54,045
621,206
kWh
|
$5,086
-
kW-mo/yr
|
- | |
02 | 2.3192: Use fossil fuel powered generator during peak demand periods | $20,908 | $14,359 |
$16,254
186,833
kWh
|
$4,654
-
kW-mo/yr
|
- | |
03 | 2.3141: Use battery storage for demand control | $11,217 | $21,658 |
$783
9,000
kWh
|
- | $10,434 | |
04 | 2.6231: Utilize controls to operate equipment only when needed | $12,033 | $25,340 |
$12,033
138,317
kWh
|
- | - | |
05 | 2.4239: Eliminate or reduce compressed air usage | $8,280 | - |
$8,280
95,171
kWh
|
- | - | |
06 | 2.4224: Upgrade controls on compressors | $5,844 | $6,000 |
$5,844
67,177
kWh
|
- | - | |
07 | 4.112: Replace old machine with new automatic multi-station tool | $38,400 | $100,000 | - | - | $38,400 | |
08 | 4.661: Level zero – install control systems for existing equipment | $23,221 | $60,000 |
$23,221
266,905
kWh
|
- | - | |
TOTAL RECOMMENDED | $179,034 | $549,965 |
$120,460
1,384,609
kWh
|
$9,740
-
kW-mo/yr
|
$48,834 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs