Assessment Year | 2023 |
---|---|
Principal Product | Plastic Bottles |
NAICS | 326160: Plastics Bottle Manufacturing |
SIC | 3085: Plastics Bottles |
Sales Range | $10 M to 50M |
# of Employees | 36 |
Plant Area |
80,000
ft2
|
Annual Production | 114,211,000
units
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $622,469 | 16,425,600 |
kWh
|
$0.038 | |
Electricity Demand | $176,149 | 18,562 |
kW-mo/yr
|
$9.49 | |
Electricity Fees | $84,912 | - |
|
- | |
Waste Disposal Costs | |||||
Water Usage | $7,158 | 4,571 |
Tgal
|
$1.57 | |
Water Disposal | $7,157 | 1,514 |
Tgal
|
$4.73 | |
TOTAL YEARLY COSTS | $897,845 | ||||
RECOMMENDED SAVINGS* | $273,225 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $180,156 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|
01 | 2.3113: Make ice during off peak hours for cooling | $73,113 | $215,600 |
$32,583
857,447
kWh
|
- | $40,530 | |
02 | 2.3191: Use demand controller or load shedder | $56,023 | $88,370 |
$43,692
1,149,792
kWh
|
$12,331
-
kW-mo/yr
|
- | |
03 | 2.4133: Use most efficient type of electric motors | $30,274 | $30,607 |
$19,195
505,136
kWh
|
$11,079
-
kW-mo/yr
|
- | |
04 | 2.5122: Replace high resistance ducts, pipes, and fittings | $15,287 | $18,600 |
$15,712
413,481
kWh
|
$(-425.0)
-
kW-mo/yr
|
- | |
05 | 2.2623: Minimize condenser cooling water temperature | $9,922 | $11,796 |
$9,922
261,100
kWh
|
- | - | |
06 | 2.6231: Utilize controls to operate equipment only when needed | $7,412 | $25,400 |
$7,412
195,050
kWh
|
- | - | |
07 | 2.1121: Use insulation in furnaces to facilitate heating / cooling | $2,981 | $508 |
$2,981
78,458
kWh
|
- | - | |
08 | 2.6127: Maintain air filters by cleaning or replacement | $1,672 | $1,200 |
$1,672
43,900
kWh
|
- | - | |
09 | 2.7447: Install vinyl strip / high speed / air curtain doors | $1,580 | $600 |
$1,580
41,592
kWh
|
- | - | |
10 | 4.661: Level zero – install control systems for existing equipment | $62,417 | $10,000 |
$62,417
1,642,560
kWh
|
- | - | |
11 | 4.663: Level two – install control system using iiot devices with communication capabilities to store data to the cloud | $12,544 | $20,214 |
$12,544
330,092
kWh
|
- | - | |
TOTAL RECOMMENDED | $273,225 | $422,895 |
$209,710
5,518,608
kWh
|
$22,985
-
kW-mo/yr
|
$40,530 | ||
TOTAL IMPLEMENTED | $180,156 | $161,681 |
$157,171
4,136,019
kWh
|
$22,985
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs