| Assessment Year | 2021 |
|---|---|
| Principal Product | Sheet Metal Work – HVAC Vents |
| NAICS | 332322: Sheet Metal Work Manufacturing |
| SIC | 3444: Sheet Metal Work |
| Sales Range | $10 M to 50M |
| # of Employees | 75 |
| Plant Area |
194,800
ft2
|
| Annual Production | 759,242
units
|
| Production Hrs. Annual | 2,314
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $126,812 | 2,152,800 |
kWh
|
$0.059 | |
| Electricity Demand | $50,643 | 8,885 |
kW-mo/yr
|
$5.70 | |
| Electricity Fees | $40,441 | - |
|
- | |
| Natural Gas | $132,221 | 10,816 |
MMBtu
|
$12.22 | |
| Waste Disposal Costs | |||||
| Water Usage | $2,242 | 423 |
Tgal
|
$5.30 | |
| Water Disposal | $298 | 12 |
Tgal
|
$24.83 | |
| TOTAL YEARLY COSTS | $352,657 | ||||
| RECOMMENDED SAVINGS* | $201,946 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | $201,946 | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings | Primary Product Savings |
|---|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $136,163 | $259,600 |
$(-1,025.0)
(-17,373)
kWh
|
- | - | - | - | $137,188 | |
| 02 | 2.2414: Use waste heat from hot flue gases to preheat | $15,219 | $20,000 | - | - |
$15,219
-
MMBtu
|
- | - | - | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $13,460 | $31,240 |
$8,967
151,984
kWh
|
$4,493
-
kW-mo/yr
|
- | - | - | - | |
| 04 | 2.4133: Use most efficient type of electric motors | $11,358 | $2,343 |
$7,760
131,522
kWh
|
$3,598
-
kW-mo/yr
|
- | - | - | - | |
| 05 | 2.7447: Install vinyl strip / high speed / air curtain doors | $7,808 | $1,360 | - | - |
$7,808
-
MMBtu
|
- | - | - | |
| 06 | 2.7134: Use photocell controls | $7,062 | $4,098 |
$7,062
119,700
kWh
|
- | - | - | - | - | |
| 07 | 2.4227: Use compressor air filters | $2,064 | $5,898 |
$2,064
34,975
kWh
|
- | - | - | - | - | |
| 08 | 2.6212: Turn off equipment during breaks, reduce operating time | $2,057 | $930 |
$2,057
34,865
kWh
|
- | - | - | - | - | |
| 09 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,043 | - |
$2,043
34,619
kWh
|
- | - | - | - | - | |
| 10 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,816 | $421 |
$1,816
30,773
kWh
|
- | - | - | - | - | |
| 11 | 2.4112: Install soft-start to eliminate nuisance trips | $1,418 | $5,192 |
$1,418
24,041
kWh
|
- | - | - | - | - | |
| 12 | 2.7133: Use separate switches on perimeter lighting which may be turned off when natural light is available | $854 | $800 |
$854
14,472
kWh
|
- | - | - | - | - | |
| 13 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $624 | - |
$425
7,212
kWh
|
- | - | $90 | $109 | - | |
| TOTAL RECOMMENDED | $201,946 | $331,882 |
$33,441
566,790
kWh
|
$8,091
-
kW-mo/yr
|
$23,027
-
MMBtu
|
$90 | $109 | $137,188 | ||
| TOTAL IMPLEMENTED | $201,946 | $331,882 |
$33,441
566,790
kWh
|
$8,091
-
kW-mo/yr
|
$23,027
-
MMBtu
|
$90 | $109 | $137,188 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings | Primary Product Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs