| Assessment Year | 2011 |
|---|---|
| Principal Product | pens |
| NAICS | 339940: Office Supplies (except Paper) Manufacturing |
| SIC | 3951: Pens, Mechanical Pencils, and Parts |
| Sales Range | $10 M to 50M |
| # of Employees | 351 |
| Plant Area |
91,000
ft2
|
| Annual Production | 290,000,000
units
|
| Production Hrs. Annual | 7,488
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $570,411 | 5,602,000 |
kWh
|
$0.10 |
| Electricity Demand | $57,901 | 12,020 |
kW-mo/yr
|
$4.82 |
| Natural Gas | $4,341 | 344 |
MMBtu
|
$12.62 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $217,840 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $18,274 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7229: Air condition only space necessary | $5,313 | $20,000 |
$5,313
47,434
kWh
|
- | |
| 02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,289 | $5,193 |
$1,289
12,636
kWh
|
- | |
| 03 | 2.7224: Reduce space conditioning during non-working hours | $17,474 | $5,800 |
$17,474
156,024
kWh
|
- | |
| 04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $15,430 | $4,040 |
$15,430
137,771
kWh
|
- | |
| 05 | 2.4239: Eliminate or reduce compressed air usage | $1,264 | $2,760 |
$1,264
11,283
kWh
|
- | |
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,983 | $11,500 |
$6,983
64,296
kWh
|
- | |
| 07 | 2.4227: Use compressor air filters | $1,555 | $847 |
$1,555
15,249
kWh
|
- | |
| 08 | 2.4224: Upgrade controls on compressors | $8,617 | $500 |
$8,617
76,937
kWh
|
- | |
| 09 | 2.4226: Use / purchase optimum sized compressor | $11,007 | $375 |
$8,683
85,132
kWh
|
$2,324
-
kW-mo/yr
|
|
| 10 | 2.4221: Install compressor air intakes in coolest locations | $1,063 | $816 |
$1,063
10,409
kWh
|
- | |
| 11 | 2.1131: Repair faulty insulation in furnaces, boilers, etc | $140,596 | $3,840 |
$140,596
1,377,040
kWh
|
- | |
| 12 | 2.7446: Utilize sensors controlling roof and wall openings | $7,249 | $4,555 |
$7,249
71,070
kWh
|
- | |
| TOTAL RECOMMENDED | $217,840 | $60,226 |
$215,516
2,065,281
kWh
|
$2,324
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | $18,274 | $10,080 |
$18,274
165,656
kWh
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs