Assessment Year | 2008 |
---|---|
Principal Product | Magazines |
NAICS | 323117: Books Printing |
SIC | 2732: Book Printing |
Sales Range | $10 M to 50M |
# of Employees | 225 |
Plant Area |
85,000
ft2
|
Annual Production | 300,000,000
pieces
|
Production Hrs. Annual | 7,488
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $568,022 | 7,743,600 |
kWh
|
$0.073 |
Electricity Demand | $57,282 | 15,474 |
kW-mo/yr
|
$3.70 |
Electricity Fees | $305 | - |
|
- |
Natural Gas | $132,408 | 9,025 |
MMBtu
|
$14.67 |
Other Gas | $59,623 | 3,495 |
MMBtu
|
$17.06 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $252,128 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $106,320 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | Primary Raw Material Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7243: Improve air circulation with destratification fans / other methods | $11,798 | $16,755 |
$11,798
161,615
kWh
|
- | - | - | - | |
02 | 2.7261: Install timers and/or thermostats | $8,549 | $1,248 |
$8,549
117,109
kWh
|
- | - | - | - | |
03 | 2.7444: Close holes and openings in building such as broken windows | $349 | $29 |
$349
4,780
kWh
|
- | - | - | - | |
04 | 2.2531: Re-size charging openings or add movable cover or door | $2,156 | $20,960 |
$2,156
26,242
kWh
|
- | - | - | - | |
05 | 2.2511: Insulate bare equipment | $764 | $2,390 | - | - |
$764
-
MMBtu
|
- | - | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $48,158 | $1,870 |
$48,158
594,538
kWh
|
- | - | - | - | |
07 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $22,082 | $24,230 |
$22,082
272,613
kWh
|
- | - | - | - | |
08 | 2.4133: Use most efficient type of electric motors | $3,400 | $10,830 |
$3,027
41,444
kWh
|
$373
-
kW-mo/yr
|
- | - | - | |
09 | 2.7226: Use computer programs to optimize hvac performance | $17,491 | $25,340 |
$17,491
239,596
kWh
|
- | - | - | - | |
10 | 2.7141: Lower light fixtures in high ceiling areas | $2,511 | $406 |
$2,347
32,148
kWh
|
$164
-
kW-mo/yr
|
- | - | - | |
11 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $1,589 | $794 |
$1,589
21,767
kWh
|
- | - | - | - | |
12 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,401 | $10,282 |
$7,823
110,685
kWh
|
$578
-
kW-mo/yr
|
- | - | - | |
13 | 2.7135: Install occupancy sensors | $1,180 | $162 |
$1,180
16,175
kWh
|
- | - | - | - | |
14 | 4.651: Install back-up equipment | $76,789 | $12,000 | - | - | - | - | $76,789 | |
15 | 3.5217: Reuse / recycle/ sell paper products | $46,911 | - | - | - | - | $46,911 | - | |
TOTAL RECOMMENDED | $252,128 | $127,296 |
$126,549
1,638,712
kWh
|
$1,115
-
kW-mo/yr
|
$764
-
MMBtu
|
$46,911 | $76,789 | ||
TOTAL IMPLEMENTED | $106,320 | $6,331 |
$58,645
738,194
kWh
|
- |
$764
-
MMBtu
|
$46,911 | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | Primary Raw Material Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs