Assessment Year | 2007 |
---|---|
Principal Product | Boats |
NAICS | 336612: Boat Building |
SIC | 3732: Boat Building and Repairing |
Sales Range | $100 M to 500M |
# of Employees | 466 |
Plant Area |
396,285,000
ft2
|
Annual Production | 495
pieces
|
Production Hrs. Annual | 4,000
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $489,589 | 6,059,520 |
kWh
|
$0.081 |
Electricity Demand | $143,300 | 16,656 |
kW-mo/yr
|
$8.60 |
Natural Gas | $9,959 | 2,668 |
MMBtu
|
$3.73 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $241,961 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $105,341 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $47,407 | $51,387 |
$36,499
450,604
kWh
|
$10,908
-
kW-mo/yr
|
- | |
02 | 2.7141: Lower light fixtures in high ceiling areas | $4,716 | $834 |
$3,581
44,160
kWh
|
$1,135
-
kW-mo/yr
|
- | |
03 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $5,532 | $545 |
$3,447
42,504
kWh
|
$2,085
-
kW-mo/yr
|
- | |
04 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $8,668 | - |
$8,668
107,016
kWh
|
- | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $19,530 | $1,396 |
$19,530
186,003
kWh
|
- | - | |
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $19,272 | - |
$19,272
183,547
kWh
|
- | - | |
07 | 2.7243: Improve air circulation with destratification fans / other methods | $49,615 | $42,263 |
$35,518
147,828
kWh
|
$14,097
-
kW-mo/yr
|
- | |
08 | 2.7261: Install timers and/or thermostats | $3,895 | $542 |
$3,895
48,090
kWh
|
- | - | |
09 | 2.7444: Close holes and openings in building such as broken windows | $1,037 | $12 |
$1,037
12,800
kWh
|
- | - | |
10 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $44,942 | $29,100 |
$44,942
554,836
kWh
|
- | - | |
11 | 2.7226: Use computer programs to optimize hvac performance | $33,577 | $25,436 |
$33,577
414,530
kWh
|
- | - | |
12 | 3.6193: Install equipment (eg compactor) to reduce disposal costs | $595 | $3,486 | - | - | $595 | |
13 | 3.6193: Install equipment (eg compactor) to reduce disposal costs | $3,175 | $8,000 | - | - | $3,175 | |
TOTAL RECOMMENDED | $241,961 | $163,001 |
$209,966
2,191,918
kWh
|
$28,225
-
kW-mo/yr
|
$3,770 | ||
TOTAL IMPLEMENTED | $105,341 | $53,882 |
$92,348
1,030,564
kWh
|
$12,993
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs