Assessment Year 2004
Principal Product Drills and Drill Rigs
NAICS 333131: Mining Machinery and Equipment Manufacturing
SIC 3532: Mining Machinery and Equipment, Except Oil and Gas Field Machinery and Equipment
Sales Range $10
M
to 50
M
# of Employees 200
Plant Area 1,750,000
ft2
Annual Production 45
pieces
Production Hrs. Annual 2,210
hrs
Location (State) Florida

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $129,680 2,146,700
kWh
Electricity Demand $38,859 6,531
kW-mo/yr
Electricity Fees $13,190 -
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $49,127 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $4,833

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Water Disposal Savings
01 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $4,833 $376 $4,833
57,080
kWh
- -
02 3.7141: Improve cleaning efficiency by maintaining cleaning system $17,356 $246 $17,356
267,017
kWh
- -
03 2.7142: Utilize higher efficiency lamps and/or ballasts $8,636 $15,747 $5,855
90,348
kWh
$2,781
-
kW-mo/yr
-
04 2.6231: Utilize controls to operate equipment only when needed $7,517 $20,000 $5,626
86,549
kWh
$1,891
-
kW-mo/yr
-
05 2.4111: Utilize energy-efficient belts and other improved mechanisms $1,081 - $1,081
11,068
kWh
- -
06 2.7141: Lower light fixtures in high ceiling areas $6,607 $200 $4,310
66,300
kWh
$2,297
-
kW-mo/yr
-
07 2.4133: Use most efficient type of electric motors $1,694 $7,494 $1,105
16,999
kWh
$589
-
kW-mo/yr
-
08 3.4155: Meter waste water $1,403 $1,500 - - $1,403
-
Tgal
TOTAL RECOMMENDED $49,127 $45,563 $40,166
595,361
kWh
$7,558
-
kW-mo/yr
$1,403
-
Tgal
TOTAL IMPLEMENTED $4,833 $376 $4,833
57,080
kWh
- -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Water Disposal Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs