| Assessment Year | 2014 |
|---|---|
| Principal Product | frozen dough |
| NAICS | 311812: Commercial Bakeries |
| SIC | 2045: Prepared Flour Mixes and Doughs |
| Sales Range | $100 M to 500M |
| # of Employees | 500 |
| Plant Area |
450,000
ft2
|
| Annual Production | 24,000,000
units
|
| Production Hrs. Annual | 8,600
hrs
|
| Location (State) | Missouri |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $2,481,084 | 31,677,111 |
kWh
|
$0.078 |
| Electricity Demand | $728,483 | 63,904 |
kW-mo/yr
|
$11.40 |
| Natural Gas | $255,499 | 55,240 |
MMBtu
|
$4.63 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $72,170 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $30,083 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7425: Clean or color roof to reduce solar load | $2,625 | $7,000 |
$2,180
27,836
kWh
|
$445
-
kW-mo/yr
|
- | |
| 02 | 2.7292: Lower ceiling to reduce conditioned space | $12,947 | $24,000 |
$11,750
150,067
kWh
|
$1,197
-
kW-mo/yr
|
- | |
| 03 | 2.2437: Recover waste heat from equipment | $3,254 | $11,500 | - | - |
$3,254
-
MMBtu
|
|
| 04 | 2.2437: Recover waste heat from equipment | $4,000 | $6,000 | - | - |
$4,000
-
MMBtu
|
|
| 05 | 2.4221: Install compressor air intakes in coolest locations | $11,440 | $2,500 |
$9,533
121,752
kWh
|
$1,907
-
kW-mo/yr
|
- | |
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $23,518 | $21,850 |
$19,545
249,615
kWh
|
$3,973
-
kW-mo/yr
|
- | |
| 07 | 2.7135: Install occupancy sensors | $10,446 | $1,875 |
$10,446
133,412
kWh
|
- | - | |
| 08 | 2.7221: Lower temperature during the winter season and vice-versa | $3,940 | - |
$3,275
41,832
kWh
|
$665
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $72,170 | $74,725 |
$56,729
724,514
kWh
|
$8,187
-
kW-mo/yr
|
$7,254
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $30,083 | $28,850 |
$25,000
319,283
kWh
|
$5,083
-
kW-mo/yr
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs