| Assessment Year | 2003 |
|---|---|
| Principal Product | Newspaper |
| NAICS | 511110: Newspaper Publishers |
| SIC | 2711: Newspapers: Publishing, or Publishing and Printing |
| Sales Range | $10 M to 50M |
| # of Employees | 210 |
| Plant Area |
70,000
ft2
|
| Annual Production | 600,000
pieces
|
| Production Hrs. Annual | 3,500
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $248,605 | 3,551,100 |
kWh
|
$0.070 |
| Electricity Demand | $5,613 | 115 |
kW-mo/yr
|
$48.81 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $79,076 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $31,740 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.7133: Use separate switches on perimeter lighting which may be turned off when natural light is available | $6,710 | $5,529 |
$6,710
84,937
kWh
|
- | - | - | - | - | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $11,048 | $39,293 |
$8,688
142,420
kWh
|
$2,360
-
kW-mo/yr
|
- | - | - | - | |
| 03 | 2.7145: Install skylights | $2,373 | $4,104 |
$1,733
28,404
kWh
|
$692
-
kW-mo/yr
|
- | - | $(-52.0) | - | |
| 04 | 2.7132: Install timers on light switches in little used areas | $1,100 | $1,073 |
$1,100
18,035
kWh
|
- | - | - | - | - | |
| 05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $993 | - |
$993
12,567
kWh
|
- | - | - | - | - | |
| 06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,383 | $340 |
$2,383
30,161
kWh
|
- | - | - | - | - | |
| 07 | 2.4151: Develop a repair/replace policy | $4,496 | $4,860 |
$3,540
58,035
kWh
|
$956
-
kW-mo/yr
|
- | - | - | - | |
| 08 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $3,247 | - |
$3,068
38,830
kWh
|
- | - | - | $23 | $156 | |
| 09 | 2.6231: Utilize controls to operate equipment only when needed | $17,064 | $5,000 |
$17,064
216,000
kWh
|
- | - | - | - | - | |
| 10 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $11,300 | $41,637 |
$9,695
158,936
kWh
|
$1,605
-
kW-mo/yr
|
- | - | - | - | |
| 11 | 2.3212: Optimize plant power factor | $15,362 | $9,000 | - | - | $15,362 | - | - | - | |
| 12 | 3.5217: Reuse / recycle/ sell paper products | $3,000 | - | - | - | - |
$3,000
-
lb
|
- | - | |
| TOTAL RECOMMENDED | $79,076 | $110,836 |
$54,974
788,325
kWh
|
$5,613
-
kW-mo/yr
|
$15,362 |
$3,000
-
lb
|
$(-29.0) | $156 | ||
| TOTAL IMPLEMENTED | $31,740 | $46,977 |
$30,135
417,664
kWh
|
$1,605
-
kW-mo/yr
|
- | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings | Ancillary Material Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs