| Assessment Year | 2001 |
|---|---|
| Principal Product | Newspaper Printing and Publishing |
| NAICS |
n/a
|
| SIC | 2711: Newspapers: Publishing, or Publishing and Printing |
| Sales Range | $10 M to 50M |
| # of Employees | 400 |
| Plant Area |
800,000
ft2
|
| Annual Production | 28,000,000
pieces
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $116,852 | 5,480,400 |
kWh
|
$0.021 |
| Electricity Demand | $117,010 | 12,354 |
kW-mo/yr
|
$9.47 |
| Fuel Oil #2 | $1,517 | - |
|
- |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $308,984 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $30,433 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings | Primary Product Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $33,061 | $50,725 |
$33,061
674,722
kWh
|
- | - | - | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,622 | $1,402 |
$1,497
71,280
kWh
|
$1,125
-
kW-mo/yr
|
- | - | |
| 03 | 2.7447: Install vinyl strip / high speed / air curtain doors | $5,786 | $2,400 |
$5,786
118,076
kWh
|
- | - | - | |
| 04 | 2.4151: Develop a repair/replace policy | $3,709 | $2,520 |
$2,209
106,872
kWh
|
$1,500
-
kW-mo/yr
|
- | - | |
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,886 | $410 |
$2,940
60,017
kWh
|
- | $(-54.0) | - | |
| 06 | 2.4235: Remove or close off unneeded compressed air lines | $1,597 | - |
$1,597
32,585
kWh
|
- | - | - | |
| 07 | 4.652: Replace existing equipment with more suitable substitutes | $2,098 | - |
$1,383
65,901
kWh
|
- | $715 | - | |
| 08 | 2.7135: Install occupancy sensors | $855 | $553 |
$855
40,732
kWh
|
- | - | - | |
| 09 | 2.2612: Use cooling tower water instead of refrigeration | $19,370 | $90,464 |
$18,650
380,616
kWh
|
- | $720 | - | |
| 10 | 3.5316: Contract a wood pallet recycling company | $1,800 | - | - | - | $1,800 | - | |
| 11 | 4.515: Install shelves / racks to utilize unused space | $168,000 | $240 | - | - | - | $168,000 | |
| 12 | 4.711: Initiate a total quality management program | $67,200 | $9,733 | - | - | - | $67,200 | |
| TOTAL RECOMMENDED | $308,984 | $158,447 |
$67,978
1,550,801
kWh
|
$2,625
-
kW-mo/yr
|
$3,181 | $235,200 | ||
| TOTAL IMPLEMENTED | $30,433 | $94,819 |
$26,788
610,704
kWh
|
$1,125
-
kW-mo/yr
|
$2,520 | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings | Primary Product Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs