| Assessment Year | 1993 |
|---|---|
| Principal Product | Plastic Closures |
| NAICS |
n/a
|
| SIC | 3089: Plastics Products, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 150 |
| Plant Area |
80,000
ft2
|
| Annual Production | 500,000,000
pieces
|
| Production Hrs. Annual | 7,500
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $526,228 | 9,078,253 |
kWh
|
$0.058 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $51,445 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $25,168 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
|---|---|---|---|---|---|
| 01 | 2.6221: Use most efficient equipment at it's maximum capacity and less efficient equipment only when necessary | $10,702 | $15,600 |
$10,702
184,642
kWh
|
|
| 02 | 2.2511: Insulate bare equipment | $4,866 | $2,520 |
$4,866
83,822
kWh
|
|
| 03 | 2.4133: Use most efficient type of electric motors | $7,941 | $8,198 |
$7,941
136,870
kWh
|
|
| 04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $3,961 | $6,100 |
$3,961
68,288
kWh
|
|
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $9,113 | $2,339 |
$9,113
152,110
kWh
|
|
| 06 | 2.7144: Install spectral reflectors / delamp | $4,406 | $6,730 |
$4,406
61,841
kWh
|
|
| 07 | 2.7135: Install occupancy sensors | $1,008 | $128 |
$1,008
22,274
kWh
|
|
| 08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $433 | $548 |
$433
6,155
kWh
|
|
| 09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,413 | $14,097 |
$3,413
58,910
kWh
|
|
| 10 | 2.7232: Replace existing hvac unit with high efficiency model | $1,036 | $1,025 |
$1,036
17,878
kWh
|
|
| 11 | 2.7261: Install timers and/or thermostats | $803 | $945 |
$803
17,878
kWh
|
|
| 12 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $3,248 | - |
$3,248
-
kWh
|
|
| 13 | 2.6231: Utilize controls to operate equipment only when needed | $515 | $1,000 |
$515
11,430
kWh
|
|
| TOTAL RECOMMENDED | $51,445 | $59,230 |
$51,445
822,098
kWh
|
||
| TOTAL IMPLEMENTED | $25,168 | $13,057 |
$25,168
372,802
kWh
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs