Assessment Year | 2024 |
---|---|
Principal Product | Heavy Gauge Custom Plastic Sheeting |
NAICS | 326113: Unlaminated Plastics Film and Sheet (except Packaging) Manufacturing |
SIC | 3081: Unsupported Plastics Film and Sheet |
Sales Range | $50 M to 100M |
# of Employees | 93 |
Plant Area |
72,000
ft2
|
Annual Production | 54,000,000
lb
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Ohio |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $582,251 | 13,171,200 |
kWh
|
$0.044 | |
Electricity Demand | $387,947 | 25,142 |
kW-mo/yr
|
$15.43 | |
Electricity Fees | $1,662 | - |
|
- | |
Natural Gas | $56,406 | 5,192 |
MMBtu
|
$10.86 | |
Waste Disposal Costs | |||||
Water Usage | $86,375 | 3,036 |
Tgal
|
$28.45 | |
Water Disposal | $5,311 | 644 |
Tgal
|
$8.25 | |
Other Liquid (non-haz) | $10,058 | 1 |
gal
|
$10,058.00 | |
TOTAL YEARLY COSTS | $1,130,010 | ||||
RECOMMENDED SAVINGS* | $86,022 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $22,137 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.4239: Eliminate or reduce compressed air usage | $19,375 | $11,280 |
$19,375
438,359
kWh
|
- | |
02 | 2.4221: Install compressor air intakes in coolest locations | $1,777 | $1,275 |
$1,202
27,199
kWh
|
$575
-
kW-mo/yr
|
|
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,691 | - |
$1,144
25,873
kWh
|
$547
-
kW-mo/yr
|
|
04 | 2.4239: Eliminate or reduce compressed air usage | $1,651 | $1,800 |
$1,651
37,363
kWh
|
- | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,111 | $952 |
$740
17,535
kWh
|
$371
-
kW-mo/yr
|
|
06 | 2.6231: Utilize controls to operate equipment only when needed | $60,417 | $127,158 |
$30,877
698,584
kWh
|
$29,540
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $86,022 | $142,465 |
$54,989
1,244,913
kWh
|
$31,033
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $22,137 | $14,032 |
$21,766
493,257
kWh
|
$371
-
kW-mo/yr
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs