Assessment Year | 2023 |
---|---|
Principal Product | Cast Acrylic |
NAICS | 326113: Unlaminated Plastics Film and Sheet (except Packaging) Manufacturing |
SIC | 3081: Unsupported Plastics Film and Sheet |
Sales Range | $10 M to 50M |
# of Employees | 11 |
Plant Area |
83,000
ft2
|
Annual Production | 2,500,000
lb
|
Production Hrs. Annual | 2,080
hrs
|
Location (State) | Ohio |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $21,742 | 457,242 |
kWh
|
$0.048 | |
Electricity Demand | $9,291 | 1,847 |
kW-mo/yr
|
$5.03 | |
Electricity Fees | $5,467 | - |
|
- | |
Natural Gas | $37,974 | 4,782 |
MMBtu
|
$7.94 | |
Waste Disposal Costs | |||||
Water Usage | $295 | 38 |
Tgal
|
$7.76 | |
Water Disposal | $272 | 38 |
Tgal
|
$7.16 | |
TOTAL YEARLY COSTS | $75,041 | ||||
RECOMMENDED SAVINGS* | $1,789,790 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $18,942 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings | Primary Product Savings |
---|---|---|---|---|---|---|---|---|---|---|---|
01 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $74 | - |
$46
958
kWh
|
$28
-
kW-mo/yr
|
- | - | - | - | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,248 | $500 |
$44
934
kWh
|
$1,204
-
kW-mo/yr
|
- | - | - | - | - | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $310 | - |
$193
4,047
kWh
|
$117
-
kW-mo/yr
|
- | - | - | - | - | |
04 | 2.4221: Install compressor air intakes in coolest locations | $242 | $500 |
$150
3,161
kWh
|
$92
-
kW-mo/yr
|
- | - | - | - | - | |
05 | 2.7444: Close holes and openings in building such as broken windows | $11,624 | $1,500 | - | - | - |
$11,624
-
MMBtu
|
- | - | - | |
06 | 2.7135: Install occupancy sensors | $1,142 | $9,668 |
$999
20,981
kWh
|
- | - | - | $143 | - | - | |
07 | 2.7122: Disconnect ballasts | $172 | $240 |
$150
3,154
kWh
|
$22
-
kW-mo/yr
|
- | - | - | - | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $933 | $7,594 |
$643
13,505
kWh
|
$190
-
kW-mo/yr
|
- | - | $34 | $66 | - | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,823 | $44,209 |
$2,336
49,066
kWh
|
$1,424
-
kW-mo/yr
|
- | - | $86 | $(-23.0) | - | |
10 | 2.3212: Optimize plant power factor | $1,467 | $7,400 | - | - | $1,467 | - | - | - | - | |
11 | 2.4324: Replace hydraulic / pneumatic equipment with electric equipment | $1,768,755 | $300,000 |
$1,974
41,476
kWh
|
$1,781
-
kW-mo/yr
|
- | - | - | - | $1,765,000 | |
TOTAL RECOMMENDED | $1,789,790 | $371,611 |
$6,535
137,282
kWh
|
$4,858
-
kW-mo/yr
|
$1,467 |
$11,624
-
MMBtu
|
$263 | $43 | $1,765,000 | ||
TOTAL IMPLEMENTED | $18,942 | $63,711 |
$4,172
87,640
kWh
|
$2,840
-
kW-mo/yr
|
- |
$11,624
-
MMBtu
|
$263 | $43 | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings | Primary Product Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs