Assessment Year | 2015 |
---|---|
Principal Product | Monolithic Refractories |
NAICS | 327120: Clay Building Material and Refractories Manufacturing |
SIC | 3297: Nonclay Refractories |
Sales Range | $100 M to 500M |
# of Employees | 200 |
Plant Area |
500,000
ft2
|
Annual Production | 167,000,000
lb
|
Production Hrs. Annual | 5,800
hrs
|
Location (State) | Ohio |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $293,650 | 3,597,022 |
kWh
|
$0.082 |
Electricity Demand | $98,145 | 12,300 |
kW-mo/yr
|
$7.98 |
Natural Gas | $69,361 | 8,976 |
MMBtu
|
$7.73 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $62,229 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $10,732 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $8,087 | - |
$7,259
104,038
kWh
|
- | $828 | |
02 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $6,573 | $2,850 |
$6,573
94,215
kWh
|
- | - | |
03 | 2.7124: Make a practice of turning off lights when not needed | $1,253 | - |
$1,125
16,128
kWh
|
- | $128 | |
04 | 2.4221: Install compressor air intakes in coolest locations | $5,762 | $2,000 |
$5,655
81,055
kWh
|
$107
-
kW-mo/yr
|
- | |
05 | 2.4239: Eliminate or reduce compressed air usage | $114 | $150 |
$93
1,328
kWh
|
$21
-
kW-mo/yr
|
- | |
06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $32,682 | $20,800 |
$25,667
367,876
kWh
|
$7,015
-
kW-mo/yr
|
- | |
07 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $3,268 | $4,200 |
$2,567
36,788
kWh
|
$701
-
kW-mo/yr
|
- | |
08 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $3,212 | $3,075 |
$2,616
37,498
kWh
|
$596
-
kW-mo/yr
|
- | |
09 | 2.4151: Develop a repair/replace policy | $330 | $1,911 |
$222
3,182
kWh
|
$108
-
kW-mo/yr
|
- | |
10 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $948 | - |
$772
11,072
kWh
|
$176
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $62,229 | $34,986 |
$52,549
753,180
kWh
|
$8,724
-
kW-mo/yr
|
$956 | ||
TOTAL IMPLEMENTED | $10,732 | $2,061 |
$9,471
135,748
kWh
|
$305
-
kW-mo/yr
|
$956 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs