| Assessment Year | 2012 |
|---|---|
| Principal Product | Load, torque, and pressure sensors |
| NAICS | 334513: Instruments and Related Products Manufacturing for Measuring, Displaying, and Controlling Industrial |
| SIC | 3823: Industrial Instruments for Measurement, Display, and Control of Process Variables; and Related Products |
| Sales Range | $10 M to 50M |
| # of Employees | 250 |
| Plant Area |
76,000
ft2
|
| Annual Production | 18,586
pieces
|
| Production Hrs. Annual | 6,400
hrs
|
| Location (State) | Ohio |
| View Case Study | |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $229,701 | 2,902,800 |
kWh
|
$0.079 |
| Electricity Demand | $24,985 | 6,864 |
kW-mo/yr
|
$3.64 |
| Natural Gas | $10,978 | 1,442 |
MMBtu
|
$7.61 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $31,249 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $22,468 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.9114: Use solar heat to make electricty | $2,058 | $42,695 |
$2,058
29,041
kWh
|
- | - | - | - | |
| 02 | 2.7135: Install occupancy sensors | $2,432 | $750 |
$2,432
29,974
kWh
|
- | - | - | - | |
| 03 | 2.7123: Keep lamps and reflectors clean | $362 | $374 |
$328
3,960
kWh
|
$34
-
kW-mo/yr
|
- | - | - | |
| 04 | 2.4224: Upgrade controls on compressors | $15,877 | $33,000 |
$877
12,375
kWh
|
- | - | - | $15,000 | |
| 05 | 2.2437: Recover waste heat from equipment | $827 | $1,000 |
$(-63.0)
885
kWh
|
$(-8.0)
-
kW-mo/yr
|
$898
-
MMBtu
|
- | - | |
| 06 | 2.4239: Eliminate or reduce compressed air usage | $648 | - |
$570
8,043
kWh
|
$78
-
kW-mo/yr
|
- | - | - | |
| 07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $452 | $1,000 |
$661
9,325
kWh
|
$91
-
kW-mo/yr
|
- | $(-300.0) | - | |
| 08 | 2.7241: Install outside air damper / economizer on hvac unit | $3,375 | $20,000 |
$1,754
24,752
kWh
|
- |
$1,621
-
MMBtu
|
- | - | |
| 09 | 2.7314: Reduce ventilation air | $2,781 | $200 |
$1,013
14,293
kWh
|
- |
$1,768
-
MMBtu
|
- | - | |
| 10 | 2.7241: Install outside air damper / economizer on hvac unit | $2,348 | $9,000 |
$2,348
33,121
kWh
|
- | - | - | - | |
| 11 | 2.7264: Interlock heating and air conditioning systems to prevent simultaneous operation | $89 | $145 |
$41
576
kWh
|
- |
$48
-
MMBtu
|
- | - | |
| TOTAL RECOMMENDED | $31,249 | $108,164 |
$12,019
166,345
kWh
|
$195
-
kW-mo/yr
|
$4,335
-
MMBtu
|
$(-300.0) | $15,000 | ||
| TOTAL IMPLEMENTED | $22,468 | $43,574 |
$5,797
81,117
kWh
|
$203
-
kW-mo/yr
|
$1,768
-
MMBtu
|
$(-300.0) | $15,000 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | Ancillary Material Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs