Assessment Year 2026
Principal Product Custom precision machined parts and complete machines
NAICS 333514: Special Die and Tool, Die Set, Jig, and Fixture Manufacturing
SIC 3544: Special Dies and Tools, Die Sets, Jigs and Fixtures, and Industrial Molds
Sales Range $5
M
to 10
M
# of Employees 37
Plant Area 100,000
ft2
Annual Production 1,000,000
units
Production Hrs. Annual 2,080
hrs
Location (State) Massachusetts

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $82,907 408,758
kWh
Electricity Demand $27,067 1,752
kW-mo/yr
Electricity Fees $1,700 -
Natural Gas $75,633 4,815
MMBtu
TOTAL YEARLY COSTS $187,308
RECOMMENDED SAVINGS* $1,351,098 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Natural Gas Savings Administrative Changes Savings
01 2.3212: Optimize plant power factor $732 $2,589 - - $732 - -
02 2.4322: Use or replace with energy efficient substitutes $3,758 $23,500 $4,378
21,590
kWh
$(-620.0)
-
kW-mo/yr
- - -
03 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $1,962 $1,575 $1,714
8,455
kWh
$248
-
kW-mo/yr
- - -
04 2.4239: Eliminate or reduce compressed air usage $4,087 $1,538 $3,590
17,702
kWh
$497
-
kW-mo/yr
- - -
05 3.7312: Implement a regular maintenance program to reduce emissions from leaky valves and pipe fittings $1,404 $150 $1,715
8,455
kWh
$249
-
kW-mo/yr
- - $(-560.0)
06 2.2437: Recover waste heat from equipment $2,451 $4,000 - - - $2,451
-
MMBtu
-
07 2.7444: Close holes and openings in building such as broken windows $11,814 $19,000 - - - $11,814
-
MMBtu
-
08 2.7134: Use photocell controls $344 $945 $317
1,451
kWh
$27
-
kW-mo/yr
- - -
09 2.7124: Make a practice of turning off lights when not needed $617 - $470
2,321
kWh
$147
-
kW-mo/yr
- - -
10 2.7142: Utilize higher efficiency lamps and/or ballasts $730 $2,800 $558
2,750
kWh
$172
-
kW-mo/yr
- - -
11 2.7261: Install timers and/or thermostats $5,903 $2,000 $263
1,298
kWh
- - $5,640
-
MMBtu
-
12 2.7211: Clean and maintain refrigerant condensers and towers $17,918 $1,625 $17,867
88,101
kWh
$51
-
kW-mo/yr
- - -
13 4.611: Begin a practice of predictive / preventative maintenance $1,859 $7,400 $1,859
9,166
kWh
- - - -
14 2.9114: Use solar heat to make electricty $4,817 $600 $4,817
23,753
kWh
- - - -
15 2.9114: Use solar heat to make electricty $192,702 $652,725 $192,702
315,789
kWh
- - - -
16 4.521: Clear and rent existing space $1,100,000 $3,727,100 - - - - $1,100,000
TOTAL RECOMMENDED $1,351,098 $4,447,547 $230,250
500,831
kWh
$771
-
kW-mo/yr
$732 $19,905
-
MMBtu
$1,099,440
TOTAL IMPLEMENTED - - - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Natural Gas Savings Administrative Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs