Assessment Year | 2025 |
---|---|
Principal Product | Engineered Fasteners |
NAICS | 332999: All Other Miscellaneous Fabricated Metal Product Manufacturing |
SIC | 3492: Fluid Power Valves and Hose Fittings |
Sales Range | $100 M to 500M |
# of Employees | 316 |
Plant Area |
49,533
ft2
|
Annual Production | 8,289
units
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | Connecticut |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $363,530 | 3,052,800 |
kWh
|
$0.12 | |
Electricity Demand | $151,561 | 7,375 |
kW-mo/yr
|
$20.55 | |
Natural Gas | $453,511 | 32,342 |
MMBtu
|
$14.02 | |
Waste Disposal Costs | |||||
Water Usage | $8,823 | 1,177 |
Tgal
|
$7.50 | |
TOTAL YEARLY COSTS | $977,424 | ||||
RECOMMENDED SAVINGS* | $397,898 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,109 | $1,474 |
$6,950
58,355
kWh
|
$159
-
kW-mo/yr
|
- | - | |
02 | 2.4221: Install compressor air intakes in coolest locations | $2,290 | $2,200 |
$1,904
15,985
kWh
|
$386
-
kW-mo/yr
|
- | - | |
03 | 2.7135: Install occupancy sensors | $6,520 | $10,625 |
$6,316
52,716
kWh
|
$205
-
kW-mo/yr
|
- | - | |
04 | 2.7134: Use photocell controls | $6,789 | $14,000 |
$6,621
55,265
kWh
|
$168
-
kW-mo/yr
|
- | - | |
05 | 2.2437: Recover waste heat from equipment | $22,999 | $8,485 | - | - |
$22,999
-
MMBtu
|
- | |
06 | 2.2511: Insulate bare equipment | $3,267 | $2,180 | - | - |
$3,267
-
MMBtu
|
- | |
07 | 2.9114: Use solar heat to make electricty | $225,469 | $2,423,010 |
$225,469
1,893,107
kWh
|
- | - | - | |
08 | 2.6231: Utilize controls to operate equipment only when needed | $6,726 | $75 |
$6,726
56,469
kWh
|
- | - | - | |
09 | 2.1321: Replace fossil fuel equipment with electrical equipment | $116,730 | $360,000 |
$(-43,559.7)
(-365,740)
kWh
|
- |
$152,348
-
MMBtu
|
$7,941
-
Tgal
|
|
TOTAL RECOMMENDED | $397,898 | $2,822,049 |
$210,425
1,766,157
kWh
|
$918
-
kW-mo/yr
|
$178,615
-
MMBtu
|
$7,941
-
Tgal
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs