ITAC Assessment: UC2406
ITAC logo
ITAC Assessment: UC2406
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2024
Principal Product Dental applicators
NAICS 339114: Dental Equipment and Supplies Manufacturing
SIC 3843: Dental Equipment and Supplies
Sales Range $10
M
to 50
M
# of Employees 77
Plant Area 45,000
ft2
Annual Production 1,000,000
units
Production Hrs. Annual 6,240
hrs
Location (State) Connecticut

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $99,156 567,000
kWh
Electricity Demand $21,509 1,604
kW-mo/yr
Electricity Fees $2,508 -
Natural Gas $5,763 615
MMBtu
Waste Disposal Costs
Water Usage $4,664 313
Tgal
TOTAL YEARLY COSTS $133,600
RECOMMENDED SAVINGS* $94,295 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Natural Gas Savings
01 2.8121: Apply for tax-free status for energy purchases $4,433 - - - $4,433 -
02 2.8114: Change rate schedules or other changes in utility service $18,201 - - - $18,201 -
03 2.6231: Utilize controls to operate equipment only when needed $596 $30 $596
3,406
kWh
- - -
04 2.4231: Reduce the pressure of compressed air to the minimum required $939 $75 $844
4,824
kWh
$95
-
kW-mo/yr
- -
05 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $1,225 $1,300 $1,100
6,291
kWh
$125
-
kW-mo/yr
- -
06 2.7232: Replace existing hvac unit with high efficiency model $6,058 $56,302 $5,482
31,343
kWh
$576
-
kW-mo/yr
- -
07 2.7261: Install timers and/or thermostats $961 $979 $184
1,053
kWh
- - $777
-
MMBtu
08 2.9114: Use solar heat to make electricty $61,883 $312,628 $61,883
353,858
kWh
- - -
TOTAL RECOMMENDED $94,295 $371,314 $70,089
400,774
kWh
$796
-
kW-mo/yr
$22,634 $777
-
MMBtu
TOTAL IMPLEMENTED - - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs