Assessment Year | 2024 |
---|---|
Principal Product | Mineral Wool Insulation |
NAICS | 327993: Mineral Wool Manufacturing |
SIC | 3296: Mineral Wool |
Sales Range | $10 M to 50M |
# of Employees | 177 |
Plant Area |
200,000
ft2
|
Annual Production | 47,635,000
lb
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | Alabama |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $852,192 | 12,175,832 |
kWh
|
$0.070 |
Electricity Demand | $155,187 | 24,785 |
kW-mo/yr
|
$6.26 |
Electricity Fees | $175,530 | - |
|
- |
Natural Gas | $256,529 | 47,959 |
MMBtu
|
$5.35 |
TOTAL YEARLY COSTS | $1,439,438 | |||
RECOMMENDED SAVINGS* | $344,535 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $9,634 | $1,046 |
$7,272
103,887
kWh
|
$933
-
kW-mo/yr
|
$1,429 | - | - | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $6,645 | $1,000 |
$4,839
69,126
kWh
|
$820
-
kW-mo/yr
|
$986 | - | - | |
03 | 2.4324: Replace hydraulic / pneumatic equipment with electric equipment | $2,549 | $1,031 |
$2,171
31,019
kWh
|
- | $378 | - | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,987 | $8,591 |
$4,542
64,879
kWh
|
$557
-
kW-mo/yr
|
$888 | - | - | |
05 | 2.2437: Recover waste heat from equipment | $16,178 | $10,450 | - | - | - |
$16,178
-
MMBtu
|
- | |
06 | 2.3212: Optimize plant power factor | $8,607 | $5,049 | - | - | $1,277 | - | $7,330 | |
07 | 2.9114: Use solar heat to make electricty | $290,423 | $2,558,734 |
$236,657
3,380,813
kWh
|
$10,680
-
kW-mo/yr
|
$43,086 | - | - | |
08 | 2.7261: Install timers and/or thermostats | $1,656 | $994 |
$1,410
20,141
kWh
|
- | $246 | - | - | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,856 | $4,621 |
$2,157
30,811
kWh
|
$275
-
kW-mo/yr
|
$424 | - | - | |
TOTAL RECOMMENDED | $344,535 | $2,591,516 |
$259,048
3,700,676
kWh
|
$13,265
-
kW-mo/yr
|
$48,714 |
$16,178
-
MMBtu
|
$7,330 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs