Assessment Year | 2024 |
---|---|
Principal Product | Flat rolled steel sheet & coil |
NAICS | 331221: Rolled Steel Shape Manufacturing |
SIC | 3316: Cold-Rolled Steel Sheet, Strip, and Bars |
Sales Range | $10 M to 50M |
# of Employees | 55 |
Plant Area |
513,633
ft2
|
Annual Production | 1,500,000
units
|
Production Hrs. Annual | 4,160
hrs
|
Location (State) | Arkansas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $119,126 | 2,292,732 |
kWh
|
$0.052 | |
Electricity Demand | $39,594 | 11,005 |
kW-mo/yr
|
$3.60 | |
Natural Gas | $29,122 | 2,276 |
MMBtu
|
$12.80 | |
LPG | $16,884 | 869 |
MMBtu
|
$19.43 | |
Waste Disposal Costs | |||||
Water Usage | $3,951 | 299 |
Tgal
|
$13.21 | |
TOTAL YEARLY COSTS | $208,677 | ||||
RECOMMENDED SAVINGS* | $99,543 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | LPG Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.9114: Use solar heat to make electricty | $46,802 | $502,083 |
$46,802
900,032
kWh
|
- | - | - | - | - | |
02 | 2.1321: Replace fossil fuel equipment with electrical equipment | $21,264 | $88,000 |
$(-768.0)
(-14,773)
kWh
|
- | - |
$16,884
-
MMBtu
|
$5,148 | - | |
03 | 2.7442: Keep doors and windows shut when not on use | $9,169 | - |
$5,036
96,847
kWh
|
- |
$4,133
-
MMBtu
|
- | - | - | |
04 | 2.8114: Change rate schedules or other changes in utility service | $6,842 | - | - | - | - | - | - | $6,842 | |
05 | 2.7261: Install timers and/or thermostats | $5,922 | $7,350 |
$5,922
113,885
kWh
|
- | - | - | - | - | |
06 | 2.7135: Install occupancy sensors | $4,645 | $900 |
$4,645
89,259
kWh
|
- | - | - | - | - | |
07 | 2.6218: Turn off equipment when not in use | $4,402 | $3,250 |
$4,402
84,667
kWh
|
- | - | - | - | - | |
08 | 2.4231: Reduce the pressure of compressed air to the minimum required | $497 | $32 |
$454
8,726
kWh
|
$43
-
kW-mo/yr
|
- | - | - | - | |
TOTAL RECOMMENDED | $99,543 | $601,615 |
$66,493
1,278,643
kWh
|
$43
-
kW-mo/yr
|
$4,133
-
MMBtu
|
$16,884
-
MMBtu
|
$5,148 | $6,842 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | LPG Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs