Assessment Year | 2014 |
---|---|
Principal Product | Greeting Cards |
NAICS | 323111: Commercial Printing (except Screen and Books) |
SIC | 2771: Greeting Cards |
Sales Range | $50 M to 100M |
# of Employees | 500 |
Plant Area |
2,600,000
ft2
|
Annual Production | 500,000,000
pieces
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Arkansas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $2,472,760 | 28,837,149 |
kWh
|
$0.086 |
Electricity Demand | $116,703 | 61,640 |
kW-mo/yr
|
$1.89 |
Natural Gas | $101,290 | 15,976 |
MMBtu
|
$6.34 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $272,138 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $257,789 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4157: Establish a predictive maintenance program | $389 | $198 |
$361
4,208
kWh
|
$28
-
kW-mo/yr
|
- | - | |
02 | 2.7122: Disconnect ballasts | $3,161 | - |
$3,153
36,792
kWh
|
$8
-
kW-mo/yr
|
- | - | |
03 | 2.4224: Upgrade controls on compressors | $9,105 | $2,000 |
$9,105
106,243
kWh
|
- | - | - | |
04 | 2.4131: Size electric motors for peak operating efficiency | $11,521 | $16,000 |
$11,521
134,429
kWh
|
- | - | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $992 | $795 |
$606
7,072
kWh
|
$18
-
kW-mo/yr
|
$368 | - | |
06 | 2.4239: Eliminate or reduce compressed air usage | $158 | $60 |
$158
1,844
kWh
|
- | - | - | |
07 | 2.6218: Turn off equipment when not in use | $12,613 | $26,558 |
$12,613
147,173
kWh
|
- | - | - | |
08 | 2.7135: Install occupancy sensors | $60,310 | $80,000 |
$60,310
703,734
kWh
|
- | - | - | |
09 | 2.7425: Clean or color roof to reduce solar load | $161,902 | $257,520 |
$182,054
2,124,320
kWh
|
$11,588
-
kW-mo/yr
|
- |
$(-31,740.0)
-
MMBtu
|
|
10 | 2.6218: Turn off equipment when not in use | $957 | - |
$957
11,170
kWh
|
- | - | - | |
11 | 2.7231: Use radiant heater for spot heating | $11,030 | $17,605 | - | - | - |
$11,030
-
MMBtu
|
|
TOTAL RECOMMENDED | $272,138 | $400,736 |
$280,838
3,276,985
kWh
|
$11,642
-
kW-mo/yr
|
$368 |
$(-20,710.0)
-
MMBtu
|
||
TOTAL IMPLEMENTED | $257,789 | $383,071 |
$277,527
3,238,349
kWh
|
$11,634
-
kW-mo/yr
|
$368 |
$(-31,740.0)
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs