| Assessment Year | 2026 |
|---|---|
| Principal Product | Vinyl Windows |
| NAICS | 326199: All Other Plastics Product Manufacturing |
| SIC | 3089: Plastics Products, Not Elsewhere Classified |
| Sales Range | $100 M to 500M |
| # of Employees | 325 |
| Plant Area |
235,000
ft2
|
| Annual Production | 380,000
units
|
| Production Hrs. Annual | 4,200
hrs
|
| Location (State) | Massachusetts |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $595,692 | 3,941,880 |
kWh
|
$0.15 |
| Electricity Demand | $159,579 | 9,118 |
kW-mo/yr
|
$17.50 |
| Electricity Fees | $11,210 | - |
|
- |
| Natural Gas | $44,931 | 2,410 |
MMBtu
|
$18.65 |
| TOTAL YEARLY COSTS | $811,411 | |||
| RECOMMENDED SAVINGS* | $283,072 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $7,979 | - | - |
$7,979
-
kW-mo/yr
|
- | - | - | |
| 02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $5,928 | - |
$5,928
39,258
kWh
|
- | - | - | - | |
| 03 | 2.4221: Install compressor air intakes in coolest locations | $6,027 | $863 |
$6,027
39,913
kWh
|
- | - | - | - | |
| 04 | 3.7312: Implement a regular maintenance program to reduce emissions from leaky valves and pipe fittings | $11,856 | $2,202 |
$11,856
78,516
kWh
|
- | - | - | - | |
| 05 | 2.7135: Install occupancy sensors | $2,892 | $889 |
$2,892
19,152
kWh
|
- | - | - | - | |
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,486 | $1,983 |
$3,044
20,160
kWh
|
$1,008
-
kW-mo/yr
|
- | - | $434 | |
| 07 | 2.7447: Install vinyl strip / high speed / air curtain doors | $1,935 | $1,261 | - | - |
$1,935
-
MMBtu
|
- | - | |
| 08 | 2.4322: Use or replace with energy efficient substitutes | $660 | $565 |
$410
2,716
kWh
|
$65
-
kW-mo/yr
|
- | - | $185 | |
| 09 | 2.6211: Conserve energy by efficient use of vending machines | $1,131 | $1,261 |
$1,131
7,489
kWh
|
- | - | - | - | |
| 10 | 2.9114: Use solar heat to make electricty | $6,618 | $7,625 |
$6,618
43,830
kWh
|
- | - | - | - | |
| 11 | 3.4151: Minimize water usage | $11,059 | $38,105 | - | - | - |
$11,059
-
Tgal
|
- | |
| 12 | 2.7492: Use proper thickness of insulation on building envelope | $752 | $3,264 | - | - |
$752
-
MMBtu
|
- | - | |
| 13 | 2.7232: Replace existing hvac unit with high efficiency model | $25,628 | $119,927 |
$855
5,664
kWh
|
- |
$24,772
-
MMBtu
|
- | - | |
| 14 | 2.9114: Use solar heat to make electricty | $194,681 | $1,183,104 |
$194,681
1,289,280
kWh
|
- | - | - | - | |
| 15 | 2.7243: Improve air circulation with destratification fans / other methods | $1,440 | $10,620 |
$(-161.3)
(-1,068)
kWh
|
$(-29.4)
-
kW-mo/yr
|
$1,631
-
MMBtu
|
- | - | |
| TOTAL RECOMMENDED | $283,072 | $1,371,668 |
$233,282
1,544,911
kWh
|
$9,023
-
kW-mo/yr
|
$29,090
-
MMBtu
|
$11,059
-
Tgal
|
$618 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs