| Assessment Year | 2026 |
|---|---|
| Principal Product | CNC machined parts |
| NAICS | 332710: Machine Shops |
| SIC | 3599: Industrial and Commercial Machinery and Equipment, Not Elsewhere Classified |
| Sales Range | $5 M to 10M |
| # of Employees | 32 |
| Plant Area |
28,000
ft2
|
| Annual Production | 226
units
|
| Production Hrs. Annual | 4,030
hrs
|
| Location (State) | New York |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $31,019 | 469,168 |
kWh
|
$0.066 |
| Electricity Demand | $40,813 | 3,467 |
kW-mo/yr
|
$11.77 |
| Electricity Fees | $240 | - |
|
- |
| Natural Gas | $3,158 | 828 |
MMBtu
|
$3.82 |
| Other Gas | $272 | 1 |
MMBtu
|
$272.11 |
| Other Energy | $16,689 | 1 |
MMBtu
|
$16,688.59 |
| TOTAL YEARLY COSTS | $92,191 | |||
| RECOMMENDED SAVINGS* | $7,967 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $2,040 | - | - |
$2,040
-
kW-mo/yr
|
- | - | |
| 02 | 2.4239: Eliminate or reduce compressed air usage | $2,031 | - |
$2,031
30,768
kWh
|
- | - | - | |
| 03 | 2.8121: Apply for tax-free status for energy purchases | $192 | - | - | - | - | $192 | |
| 04 | 2.7224: Reduce space conditioning during non-working hours | $244 | - | - | - |
$244
-
MMBtu
|
- | |
| 05 | 2.4322: Use or replace with energy efficient substitutes | $437 | $16 |
$252
3,825
kWh
|
$247
-
kW-mo/yr
|
$(-62.2)
-
MMBtu
|
- | |
| 06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $808 | $41 |
$808
12,246
kWh
|
- | - | - | |
| 07 | 2.2437: Recover waste heat from equipment | $166 | $142 | - | - |
$166
-
MMBtu
|
- | |
| 08 | 2.7135: Install occupancy sensors | $577 | $574 |
$577
8,745
kWh
|
- | - | - | |
| 09 | 2.4322: Use or replace with energy efficient substitutes | $381 | $508 |
$179
2,716
kWh
|
$44
-
kW-mo/yr
|
- | $158 | |
| 10 | 2.4221: Install compressor air intakes in coolest locations | $251 | $356 |
$251
3,809
kWh
|
- | - | - | |
| 11 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $469 | $851 |
$251
3,804
kWh
|
$133
-
kW-mo/yr
|
- | $85 | |
| 12 | 2.6211: Conserve energy by efficient use of vending machines | $203 | $374 |
$203
3,066
kWh
|
- | - | - | |
| 13 | 2.7447: Install vinyl strip / high speed / air curtain doors | $167 | $334 | - | - |
$167
-
MMBtu
|
- | |
| TOTAL RECOMMENDED | $7,967 | $3,195 |
$4,553
68,980
kWh
|
$2,464
-
kW-mo/yr
|
$515
-
MMBtu
|
$435 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs