Assessment Year | 2018 |
---|---|
Principal Product | Precision Machining |
NAICS | 336412: Aircraft Engine and Engine Parts Manufacturing |
SIC | 3724: Aircraft Engines and Engine Parts |
Sales Range | $10 M to 50M |
# of Employees | 157 |
Plant Area |
150,000
ft2
|
Annual Production | 1,300,000
units
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $146,611 | 4,199,982 |
kWh
|
$0.035 | |
Electricity Demand | $88,047 | 10,845 |
kW-mo/yr
|
$8.12 | |
Electricity Fees | $6,218 | - |
|
- | |
Natural Gas | $30,287 | 4,233 |
MMBtu
|
$7.15 | |
Waste Disposal Costs | |||||
Water Usage | $92,168 | 853 |
Tgal
|
$108.00 | |
TOTAL YEARLY COSTS | $363,331 | ||||
RECOMMENDED SAVINGS* | $34,989 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $21,562 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.8121: Apply for tax-free status for energy purchases | $8,223 | - | - | - | - | - | - | $8,223 | |
02 | 2.8121: Apply for tax-free status for energy purchases | $157 | - | - | - | - | - | - | $157 | |
03 | 2.7224: Reduce space conditioning during non-working hours | $90 | - | - | - |
$90
-
MMBtu
|
- | - | - | |
04 | 2.7447: Install vinyl strip / high speed / air curtain doors | $560 | $200 | - | - |
$560
-
MMBtu
|
- | - | - | |
05 | 3.1161: Eliminate/reduce an operation | $10,228 | $2,970 | - | - | - | $6,705 | $3,523 | - | |
06 | 2.4221: Install compressor air intakes in coolest locations | $1,474 | $1,455 |
$1,474
42,105
kWh
|
- | - | - | - | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $335 | $430 |
$77
2,190
kWh
|
$24
-
kW-mo/yr
|
- | $234 | - | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $12,156 | $19,261 |
$4,453
127,231
kWh
|
$2,417
-
kW-mo/yr
|
- | $5,286 | - | - | |
09 | 2.7314: Reduce ventilation air | $1,478 | $2,495 |
$336
9,609
kWh
|
- |
$1,142
-
MMBtu
|
- | - | - | |
10 | 2.6211: Conserve energy by efficient use of vending machines | $288 | $1,051 |
$288
8,223
kWh
|
- | - | - | - | - | |
TOTAL RECOMMENDED | $34,989 | $27,862 |
$6,628
189,358
kWh
|
$2,441
-
kW-mo/yr
|
$1,792
-
MMBtu
|
$12,225 | $3,523 | $8,380 | ||
TOTAL IMPLEMENTED | $21,562 | $20,942 |
$4,818
137,644
kWh
|
$2,441
-
kW-mo/yr
|
$560
-
MMBtu
|
$5,520 | - | $8,223 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs