Assessment Year | 2017 |
---|---|
Principal Product | Contract Machine Shop |
NAICS | 332710: Machine Shops |
SIC | 3599: Industrial and Commercial Machinery and Equipment, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 88 |
Plant Area |
41,764
ft2
|
Annual Production | 390,363
units
|
Production Hrs. Annual | 7,248
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $77,900 | 1,279,350 |
kWh
|
$0.061 |
Electricity Demand | $57,693 | 1,998 |
kW-mo/yr
|
$28.88 |
Electricity Fees | $4,904 | - |
|
- |
LPG | $16,646 | 954 |
MMBtu
|
$17.45 |
Fuel Oil #2 | $4,603 | 337 |
MMBtu
|
$13.66 |
TOTAL YEARLY COSTS | $161,746 | |||
RECOMMENDED SAVINGS* | $20,753 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $9,622 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | LPG Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7122: Disconnect ballasts | $95 | - |
$26
426
kWh
|
$69
-
kW-mo/yr
|
- | - | - | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $4,538 | $388 |
$4,538
74,391
kWh
|
- | - | - | - | |
03 | 3.7312: Implement a regular maintenance program to reduce emissions from leaky valves and pipe fittings | $3,447 | $2,277 |
$3,447
56,513
kWh
|
- | - | - | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $800 | $741 |
$283
4,643
kWh
|
$185
-
kW-mo/yr
|
- | $226 | $106 | |
05 | 3.1161: Eliminate/reduce an operation | $4,066 | $4,830 |
$(-15.0)
(-253)
kWh
|
$(-693.0)
-
kW-mo/yr
|
- | $3,623 | $1,151 | |
06 | 2.7447: Install vinyl strip / high speed / air curtain doors | $5,893 | $8,240 |
$(-783.0)
(-12,830)
kWh
|
$(-2,033.0)
-
kW-mo/yr
|
$8,709
-
MMBtu
|
- | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $486 | $719 |
$243
3,985
kWh
|
$191
-
kW-mo/yr
|
- | $48 | $4 | |
08 | 2.6211: Conserve energy by efficient use of vending machines | $214 | $533 |
$214
3,504
kWh
|
- | - | - | - | |
09 | 2.4221: Install compressor air intakes in coolest locations | $1,214 | $3,195 |
$1,214
19,903
kWh
|
- | - | - | - | |
TOTAL RECOMMENDED | $20,753 | $20,923 |
$9,167
150,282
kWh
|
$(-2,281.0)
-
kW-mo/yr
|
$8,709
-
MMBtu
|
$3,897 | $1,261 | ||
TOTAL IMPLEMENTED | $9,622 | $11,043 |
$4,955
81,232
kWh
|
$(-439.0)
-
kW-mo/yr
|
- | $3,849 | $1,257 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | LPG Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs