Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $889,319 | 17,361,643 |
kWh
|
$0.051 |
Natural Gas | $59,889 | 10,804 |
MMBtu
|
$5.54 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $95,236 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $40,011 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7144: Install spectral reflectors / delamp | $4,610 | - |
$4,610
90,035
kWh
|
- | - | - | |
02 | 2.4221: Install compressor air intakes in coolest locations | $10,664 | $994 |
$10,664
208,284
kWh
|
- | - | - | |
03 | 2.7444: Close holes and openings in building such as broken windows | $1,064 | $125 |
$133
2,602
kWh
|
$931
-
MMBtu
|
- | - | |
04 | 2.7442: Keep doors and windows shut when not on use | $18,079 | $3,600 |
$2,265
44,238
kWh
|
$15,814
-
MMBtu
|
- | - | |
05 | 2.7131: Add area lighting switches | $429 | $152 |
$429
8,386
kWh
|
- | - | - | |
06 | 2.7314: Reduce ventilation air | $1,471 | $882 |
$224
4,373
kWh
|
$1,247
-
MMBtu
|
- | - | |
07 | 2.7135: Install occupancy sensors | $2,294 | $2,093 |
$2,294
44,808
kWh
|
- | - | - | |
08 | 2.7111: Reduce illumination to minimum necessary levels | $35,885 | $54,000 |
$35,885
700,877
kWh
|
- | - | - | |
09 | 3.1161: Eliminate/reduce an operation | $13,535 | $19,680 |
$(-86.0)
(-1,672)
kWh
|
- | $2,100 | $11,521 | |
10 | 2.7442: Keep doors and windows shut when not on use | $716 | $1,567 |
$90
1,757
kWh
|
$626
-
MMBtu
|
- | - | |
11 | 2.2414: Use waste heat from hot flue gases to preheat | $6,108 | $20,639 | - |
$6,108
-
MMBtu
|
- | - | |
12 | 2.6211: Conserve energy by efficient use of vending machines | $381 | $1,312 |
$381
7,433
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $95,236 | $105,044 |
$56,889
1,111,121
kWh
|
$24,726
-
MMBtu
|
$2,100 | $11,521 | ||
TOTAL IMPLEMENTED | $40,011 | $25,650 |
$9,645
188,397
kWh
|
$16,745
-
MMBtu
|
$2,100 | $11,521 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |