Assessment Year | 2007 |
---|---|
Principal Product | Electronic Instrumentation |
NAICS | 334513: Instruments and Related Products Manufacturing for Measuring, Displaying, and Controlling Industrial |
SIC | 3823: Industrial Instruments for Measurement, Display, and Control of Process Variables; and Related Products |
Sales Range | $50 M to 100M |
# of Employees | 222 |
Plant Area |
133,875
ft2
|
Annual Production | 1,960
pieces
|
Production Hrs. Annual | 3,060
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $256,678 | 3,563,455 |
kWh
|
$0.072 |
Electricity Demand | $68,249 | 7,454 |
kW-mo/yr
|
$9.16 |
Electricity Fees | $61,958 | - |
|
- |
Natural Gas | $63,891 | 55,907 |
MMBtu
|
$1.14 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $60,826 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $60,472 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|
01 | 2.6231: Utilize controls to operate equipment only when needed | $16,451 | - |
$16,451
228,480
kWh
|
- | - | |
02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $403 | - |
$321
4,459
kWh
|
$82
-
kW-mo/yr
|
- | |
03 | 2.4314: Use synthetic lubricant | $138 | - |
$111
1,544
kWh
|
$27
-
kW-mo/yr
|
- | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $125 | - |
$61
842
kWh
|
$64
-
kW-mo/yr
|
- | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $571 | $249 |
$287
3,993
kWh
|
$284
-
kW-mo/yr
|
- | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,455 | $1,114 |
$492
6,833
kWh
|
$82
-
kW-mo/yr
|
$881 | |
07 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $7,895 | $7,860 |
$7,730
107,364
kWh
|
$165
-
kW-mo/yr
|
- | |
08 | 2.7314: Reduce ventilation air | $12,057 | $13,919 |
$11,837
164,406
kWh
|
$220
-
kW-mo/yr
|
- | |
09 | 2.6211: Conserve energy by efficient use of vending machines | $354 | $630 |
$354
4,917
kWh
|
- | - | |
10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,800 | $5,887 |
$2,690
37,350
kWh
|
$110
-
kW-mo/yr
|
- | |
11 | 2.4221: Install compressor air intakes in coolest locations | $40 | $153 |
$22
306
kWh
|
$18
-
kW-mo/yr
|
- | |
12 | 2.7135: Install occupancy sensors | $368 | $1,801 |
$368
5,110
kWh
|
- | - | |
13 | 2.4322: Use or replace with energy efficient substitutes | $18,169 | $135,500 |
$15,422
214,200
kWh
|
$2,747
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $60,826 | $167,113 |
$56,146
779,804
kWh
|
$3,799
-
kW-mo/yr
|
$881 | ||
TOTAL IMPLEMENTED | $60,472 | $166,483 |
$55,792
774,887
kWh
|
$3,799
-
kW-mo/yr
|
$881 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs