ITAC Assessment: SU0260
ITAC logo
ITAC Assessment: SU0260
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2007
Principal Product Plastic Injection Moldings
NAICS 326199: All Other Plastics Product Manufacturing
SIC 3089: Plastics Products, Not Elsewhere Classified
Sales Range $100
M
to 500
M
# of Employees 490
Plant Area 264,000
ft2
Annual Production 8,300,000,000
pieces
Production Hrs. Annual 8,760
hrs
Location (State) New York

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $1,610,796 23,151,044
kWh
Electricity Demand $8,398 38,868
kW-mo/yr
Electricity Fees $158,780 -
Natural Gas $86,235 8,113
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $200,044 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $39,234

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings One-time Revenue or Avoided Cost Savings
01 2.4231: Reduce the pressure of compressed air to the minimum required $24,228 - $24,123
344,618
kWh
$105
-
kW-mo/yr
-
02 2.6231: Utilize controls to operate equipment only when needed $4,676 - $4,676
66,800
kWh
- -
03 2.8114: Change rate schedules or other changes in utility service $4,312 - - - $4,312
04 2.4322: Use or replace with energy efficient substitutes $685 - $672
9,600
kWh
$13
-
kW-mo/yr
-
05 2.4221: Install compressor air intakes in coolest locations $10,644 $1,034 $10,595
150,934
kWh
$49
-
kW-mo/yr
-
06 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $3,677 $490 $3,661
52,297
kWh
$16
-
kW-mo/yr
-
07 2.6211: Conserve energy by efficient use of vending machines $142 $739 $142
2,026
kWh
- -
08 2.4322: Use or replace with energy efficient substitutes $151,680 $914,460 - - $151,680
TOTAL RECOMMENDED $200,044 $916,723 $43,869
626,275
kWh
$183
-
kW-mo/yr
$155,992
TOTAL IMPLEMENTED $39,234 $1,524 $39,051
557,449
kWh
$183
-
kW-mo/yr
-
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings One-time Revenue or Avoided Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs