Assessment Year | 2007 |
---|---|
Principal Product | Plastic Injection Moldings |
NAICS | 326199: All Other Plastics Product Manufacturing |
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $100 M to 500M |
# of Employees | 490 |
Plant Area |
264,000
ft2
|
Annual Production | 8,300,000,000
pieces
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,610,796 | 23,151,044 |
kWh
|
$0.070 |
Electricity Demand | $8,398 | 38,868 |
kW-mo/yr
|
$0.22 |
Electricity Fees | $158,780 | - |
|
- |
Natural Gas | $86,235 | 8,113 |
MMBtu
|
$10.63 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $200,044 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $39,234 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $24,228 | - |
$24,123
344,618
kWh
|
$105
-
kW-mo/yr
|
- | |
02 | 2.6231: Utilize controls to operate equipment only when needed | $4,676 | - |
$4,676
66,800
kWh
|
- | - | |
03 | 2.8114: Change rate schedules or other changes in utility service | $4,312 | - | - | - | $4,312 | |
04 | 2.4322: Use or replace with energy efficient substitutes | $685 | - |
$672
9,600
kWh
|
$13
-
kW-mo/yr
|
- | |
05 | 2.4221: Install compressor air intakes in coolest locations | $10,644 | $1,034 |
$10,595
150,934
kWh
|
$49
-
kW-mo/yr
|
- | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,677 | $490 |
$3,661
52,297
kWh
|
$16
-
kW-mo/yr
|
- | |
07 | 2.6211: Conserve energy by efficient use of vending machines | $142 | $739 |
$142
2,026
kWh
|
- | - | |
08 | 2.4322: Use or replace with energy efficient substitutes | $151,680 | $914,460 | - | - | $151,680 | |
TOTAL RECOMMENDED | $200,044 | $916,723 |
$43,869
626,275
kWh
|
$183
-
kW-mo/yr
|
$155,992 | ||
TOTAL IMPLEMENTED | $39,234 | $1,524 |
$39,051
557,449
kWh
|
$183
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs