Assessment Year | 2002 |
---|---|
Principal Product | #9 and #10 envelopes |
NAICS |
n/a
|
SIC | 2677: Envelopes |
Sales Range | $10 M to 50M |
# of Employees | 95 |
Plant Area |
88,000
ft2
|
Annual Production | 1,040,000,000
units
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $175,934 | 2,714,100 |
kWh
|
$0.065 |
Electricity Demand | $61,416 | 6,252 |
kW-mo/yr
|
$9.82 |
Natural Gas | $15,424 | 1,342 |
MMBtu
|
$11.49 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $23,840 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $18,799 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $111 | - |
$111
1,810
kWh
|
- | - | - | |
02 | 2.7124: Make a practice of turning off lights when not needed | $429 | $71 |
$414
6,895
kWh
|
$15
-
kW-mo/yr
|
- | - | |
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $806 | $2,150 |
$806
13,418
kWh
|
- | - | - | |
04 | 2.3212: Optimize plant power factor | $923 | $3,750 | - | - | $923 | - | |
05 | 2.4221: Install compressor air intakes in coolest locations | $1,228 | $327 |
$1,228
20,465
kWh
|
- | - | - | |
06 | 2.2531: Re-size charging openings or add movable cover or door | $3,312 | $327 | - | - | - |
$3,312
-
MMBtu
|
|
07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $4,451 | - |
$4,451
74,180
kWh
|
- | - | - | |
08 | 2.6231: Utilize controls to operate equipment only when needed | $12,580 | $510 |
$12,580
262,080
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $23,840 | $7,135 |
$19,590
378,848
kWh
|
$15
-
kW-mo/yr
|
$923 |
$3,312
-
MMBtu
|
||
TOTAL IMPLEMENTED | $18,799 | $908 |
$18,784
365,430
kWh
|
$15
-
kW-mo/yr
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs