| Assessment Year | 2001 |
|---|---|
| Principal Product | Industrial Filters |
| NAICS |
n/a
|
| SIC | 3569: General Industrial Machinery and Equipment, Not Elsewhere |
| Sales Range | $5 M to 10M |
| # of Employees | 47 |
| Plant Area |
37,029
ft2
|
| Annual Production | 60
units
|
| Production Hrs. Annual | 2,080
hrs
|
| Location (State) | New York |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $26,900 | 389,280 |
kWh
|
$0.069 |
| Electricity Demand | $24,808 | 1,657 |
kW-mo/yr
|
$14.97 |
| Electricity Fees | $3,122 | - |
|
- |
| Natural Gas | $16,109 | 2,437 |
MMBtu
|
$6.61 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $11,913 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $3,269 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $92 | - |
$92
1,455
kWh
|
- | - | |
| 02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $147 | - |
$62
986
kWh
|
$85
-
kW-mo/yr
|
- | |
| 03 | 2.7111: Reduce illumination to minimum necessary levels | $3,030 | $4,460 |
$2,018
32,024
kWh
|
$1,012
-
kW-mo/yr
|
- | |
| 04 | 2.7442: Keep doors and windows shut when not on use | $8,614 | $20,500 | - | - |
$8,614
-
MMBtu
|
|
| 05 | 2.4221: Install compressor air intakes in coolest locations | $30 | $79 |
$30
480
kWh
|
- | - | |
| TOTAL RECOMMENDED | $11,913 | $25,039 |
$2,202
34,945
kWh
|
$1,097
-
kW-mo/yr
|
$8,614
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $3,269 | $4,460 |
$2,172
34,465
kWh
|
$1,097
-
kW-mo/yr
|
- | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs