| Assessment Year | 2026 |
|---|---|
| Principal Product | Natural Almonds |
| NAICS | 311911: Roasted Nuts and Peanut Butter Manufacturing |
| SIC | 2068: Salted and Roasted Nuts and Seeds |
| Sales Range | $50 M to 100M |
| # of Employees | 1 |
| Plant Area |
320,000
ft2
|
| Annual Production | 105,000,000
lb
|
| Production Hrs. Annual | 6,000
hrs
|
| Location (State) | California |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $603,610 | 4,410,618 |
kWh
|
$0.14 |
| Electricity Demand | $229,256 | 12,979 |
kW-mo/yr
|
$17.66 |
| LPG | $402,016 | 25,728 |
MMBtu
|
$15.63 |
| TOTAL YEARLY COSTS | $1,234,882 | |||
| RECOMMENDED SAVINGS* | $337,992 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | LPG Savings | Personnel Changes Savings | Primary Raw Material Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $9,092 | - |
$9,972
72,844
kWh
|
- | - | $(-880.0) | - | |
| 02 | 2.4239: Eliminate or reduce compressed air usage | $3,116 | $220 |
$1,253
9,150
kWh
|
$1,863
-
kW-mo/yr
|
- | - | - | |
| 03 | 2.1233: Analyze flue gas for proper air/fuel ratio | $2,578 | - | - | - |
$3,328
-
MMBtu
|
$(-750.0) | - | |
| 04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $11,258 | $6,264 |
$11,258
82,233
kWh
|
- | - | - | - | |
| 05 | 2.7224: Reduce space conditioning during non-working hours | $5,987 | $5,606 |
$5,987
43,734
kWh
|
- | - | - | - | |
| 06 | 2.2511: Insulate bare equipment | $38,998 | $38,922 | - | - |
$38,998
-
MMBtu
|
- | - | |
| 07 | 2.6231: Utilize controls to operate equipment only when needed | $1,544 | $4,130 |
$1,544
11,280
kWh
|
- | - | - | - | |
| 08 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $16,383 | $49,958 |
$16,383
119,669
kWh
|
- | - | - | - | |
| 09 | 2.7124: Make a practice of turning off lights when not needed | $788 | $2,785 |
$624
4,562
kWh
|
- | - | $67 | $97 | |
| 10 | 2.2427: Use waste heat from hot flue gases to preheat incoming fluids | $6,422 | $29,062 | - | - |
$6,422
-
MMBtu
|
- | - | |
| 11 | 2.9114: Use solar heat to make electricty | $241,826 | $1,576,614 |
$241,826
1,783,014
kWh
|
- | - | - | - | |
| TOTAL RECOMMENDED | $337,992 | $1,713,561 |
$288,847
2,126,486
kWh
|
$1,863
-
kW-mo/yr
|
$48,748
-
MMBtu
|
$(-1,563.0) | $97 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | LPG Savings | Personnel Changes Savings | Primary Raw Material Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs