| Assessment Year | 2016 |
|---|---|
| Principal Product | Automotive service equipment |
| NAICS | 334515: Instrument Manufacturing for Measuring and Testing Electricity and Electrical Signals |
| SIC | 3825: Instruments for Measuring and Testing of Electricity and Electrical Signals |
| Sales Range | $10 M to 50M |
| # of Employees | 205 |
| Plant Area |
207,000
ft2
|
| Annual Production | 40,000
units
|
| Production Hrs. Annual | 2,125
hrs
|
| Location (State) | Missouri |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $271,798 | 3,305,007 |
kWh
|
$0.082 |
| Electricity Demand | $22,613 | 8,975 |
kW-mo/yr
|
$2.52 |
| Natural Gas | $88,087 | 7,914 |
MMBtu
|
$11.13 |
| TOTAL YEARLY COSTS | $382,498 | |||
| RECOMMENDED SAVINGS* | $71,353 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $35,384 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 4.512: Condense operation into one building | $4,197 | $900 |
$4,197
51,060
kWh
|
- | - | |
| 02 | 2.7221: Lower temperature during the winter season and vice-versa | $27,674 | $30,000 |
$25,704
312,699
kWh
|
$1,970
-
kW-mo/yr
|
- | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $23,739 | $80,500 |
$20,236
246,181
kWh
|
$3,503
-
kW-mo/yr
|
- | |
| 04 | 2.7135: Install occupancy sensors | $6,607 | $3,000 |
$6,607
80,385
kWh
|
- | - | |
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $841 | $1,100 |
$717
8,719
kWh
|
$124
-
kW-mo/yr
|
- | |
| 06 | 2.2426: Use waste heat from flue gases to heat space conditioning air | $7,627 | $20,000 | - | - |
$7,627
-
MMBtu
|
|
| 07 | 2.2511: Insulate bare equipment | $668 | $600 | - | - |
$668
-
MMBtu
|
|
| TOTAL RECOMMENDED | $71,353 | $136,100 |
$57,461
699,044
kWh
|
$5,597
-
kW-mo/yr
|
$8,295
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $35,384 | $85,500 |
$31,757
386,345
kWh
|
$3,627
-
kW-mo/yr
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs