Assessment Year | 2025 |
---|---|
Principal Product | Laboratory Equipment |
NAICS | 334516: Analytical Laboratory Instrument Manufacturing |
SIC | 3826: Laboratory Analytical Instruments |
Sales Range | greater than $500 M |
# of Employees | 650 |
Plant Area |
540,000
ft2
|
Annual Production | 250,000,000
units
|
Production Hrs. Annual | 4,680
hrs
|
Location (State) | Nevada |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,664,430 | 13,052,389 |
kWh
|
$0.13 |
Natural Gas | $116,493 | 11,428 |
MMBtu
|
$10.19 |
TOTAL YEARLY COSTS | $1,780,923 | |||
RECOMMENDED SAVINGS* | $456,802 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $23,708 | $800 |
$23,708
185,945
kWh
|
|
02 | 2.6218: Turn off equipment when not in use | $19,341 | - |
$19,341
151,698
kWh
|
|
03 | 2.6218: Turn off equipment when not in use | $17,910 | - |
$17,910
140,473
kWh
|
|
04 | 2.6231: Utilize controls to operate equipment only when needed | $15,669 | $1,600 |
$15,669
122,891
kWh
|
|
05 | 2.4239: Eliminate or reduce compressed air usage | $3,127 | $2,635 |
$3,127
24,528
kWh
|
|
06 | 2.4221: Install compressor air intakes in coolest locations | $648 | $1,387 |
$648
5,084
kWh
|
|
07 | 2.9114: Use solar heat to make electricty | $376,399 | $2,178,800 |
$376,399
2,952,147
kWh
|
|
TOTAL RECOMMENDED | $456,802 | $2,185,222 |
$456,802
3,582,766
kWh
|
||
TOTAL IMPLEMENTED | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs