Assessment Year 2011
Principal Product Capsules
NAICS 322220: Paper Bag and Coated and Treated Paper Manufacturing
SIC 2671: Packaging Paper and Plastics Film, Coated and Laminated
Sales Range $10
M
to 50
M
# of Employees 100
Plant Area 100,000
ft2
Annual Production 700,000,000
pieces
Production Hrs. Annual 6,888
hrs
Location (State) California

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $216,796 2,662,102
kWh
Electricity Demand $26,014 4,752
kW-mo/yr
Electricity Fees $4,256 -
Natural Gas $78,293 9,745
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $26,200 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $7,972

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
01 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $2,239 $720 $2,239
27,511
kWh
- -
02 2.7232: Replace existing hvac unit with high efficiency model $1,307 $2,006 $1,307
16,061
kWh
- -
03 2.4239: Eliminate or reduce compressed air usage $681 $1,471 $681
8,365
kWh
- -
04 2.1311: Replace electrically-operated equipment with fossil fuel equipment $8,148 $20,097 $10,040
123,342
kWh
$2,355
-
kW-mo/yr
$(-4,247.0)
-
MMBtu
05 2.6231: Utilize controls to operate equipment only when needed $5,026 $14,750 $5,026
61,740
kWh
- -
06 2.7135: Install occupancy sensors $1,801 $5,900 $1,465
17,993
kWh
$336
-
kW-mo/yr
-
07 2.6231: Utilize controls to operate equipment only when needed $4,142 $15,378 $4,142
50,885
kWh
- -
08 2.4226: Use / purchase optimum sized compressor $1,944 $9,877 $1,944
23,877
kWh
- -
09 2.7134: Use photocell controls $912 $5,037 $706
8,667
kWh
$206
-
kW-mo/yr
-
TOTAL RECOMMENDED $26,200 $75,236 $27,550
338,441
kWh
$2,897
-
kW-mo/yr
$(-4,247.0)
-
MMBtu
TOTAL IMPLEMENTED $7,972 $19,974 $7,636
93,807
kWh
$336
-
kW-mo/yr
-
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs