Assessment Year | 2010 |
---|---|
Principal Product | Rubber Roofing and Flooring |
NAICS | 326199: All Other Plastics Product Manufacturing |
SIC | 3069: Fabricated Rubber Products, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 200 |
Plant Area |
130,000
ft2
|
Annual Production | 25,000,000
lb
|
Production Hrs. Annual | 6,120
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $547,823 | 5,680,000 |
kWh
|
$0.096 |
Electricity Demand | $313,818 | 19,032 |
kW-mo/yr
|
$16.49 |
Natural Gas | $300,618 | 37,486 |
MMBtu
|
$8.02 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $137,760 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $121,868 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.6212: Turn off equipment during breaks, reduce operating time | $1,708 | - | - | - | - |
$1,708
-
MMBtu
|
|
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $9,828 | - |
$9,828
101,951
kWh
|
- | - | - | |
03 | 2.7229: Air condition only space necessary | $14,706 | $3,207 |
$14,706
152,549
kWh
|
- | - | - | |
04 | 2.4239: Eliminate or reduce compressed air usage | $7,023 | $1,764 |
$3,501
36,311
kWh
|
$3,522
-
kW-mo/yr
|
- | - | |
05 | 2.2511: Insulate bare equipment | $24,404 | $7,250 |
$19,773
205,028
kWh
|
$4,631
-
kW-mo/yr
|
- | - | |
06 | 2.6231: Utilize controls to operate equipment only when needed | $1,991 | $789 |
$1,991
20,642
kWh
|
- | - | - | |
07 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $11,024 | $5,560 |
$11,024
114,358
kWh
|
- | - | - | |
08 | 2.2511: Insulate bare equipment | $4,611 | $2,176 | - | - | - |
$4,611
-
MMBtu
|
|
09 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $326 | $261 |
$244
2,530
kWh
|
$82
-
kW-mo/yr
|
- | - | |
10 | 2.2511: Insulate bare equipment | $996 | $821 | - | - | - |
$996
-
MMBtu
|
|
11 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $3,039 | $2,749 |
$3,039
31,518
kWh
|
- | - | - | |
12 | 2.4227: Use compressor air filters | $2,168 | $3,000 |
$2,168
22,489
kWh
|
- | - | - | |
13 | 2.3511: Use plant owned transformers or lease transformers | $39,251 | $58,106 | - | - | $39,251 | - | |
14 | 2.4239: Eliminate or reduce compressed air usage | $846 | $1,500 |
$453
4,700
kWh
|
$393
-
kW-mo/yr
|
- | - | |
15 | 2.7134: Use photocell controls | $1,030 | $2,587 |
$538
5,580
kWh
|
$492
-
kW-mo/yr
|
- | - | |
16 | 2.7135: Install occupancy sensors | $2,946 | $75 |
$1,762
18,279
kWh
|
$1,184
-
kW-mo/yr
|
- | - | |
17 | 2.1243: Use heat from boiler blowdown to preheat boiler feed water | $6,167 | $17,310 | - | - | - |
$6,167
-
MMBtu
|
|
18 | 2.3212: Optimize plant power factor | $5,696 | $21,908 | - | - | $5,696 | - | |
TOTAL RECOMMENDED | $137,760 | $129,063 |
$69,027
715,935
kWh
|
$10,304
-
kW-mo/yr
|
$44,947 |
$13,482
-
MMBtu
|
||
TOTAL IMPLEMENTED | $121,868 | $106,920 |
$66,568
690,426
kWh
|
$8,645
-
kW-mo/yr
|
$44,947 |
$1,708
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs