Assessment Year | 1993 |
---|---|
Principal Product | CANNED, BOTTLED BEVERAGE |
NAICS |
n/a
|
SIC | 2086: Bottled and Canned Soft Drinks and Carbonated Waters |
Sales Range | $50 M to 100M |
# of Employees | 337 |
Plant Area |
n/a
|
Annual Production | 18,000,000
pieces
|
Production Hrs. Annual | 3,990
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $506,671 | 6,006,448 |
kWh
|
$0.084 |
Natural Gas | $77,715 | 15,444 |
MMBtu
|
$5.03 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $107,787 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $25,875 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.4133: Use most efficient type of electric motors | $1,020 | $3,197 |
$1,020
12,016
kWh
|
- | - | |
02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $4,867 | $8,765 |
$4,867
57,737
kWh
|
- | - | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,602 | $20 |
$1,602
19,050
kWh
|
- | - | |
04 | 2.2444: Use hot process fluids to preheat incoming process fluids | $35,110 | $13,450 |
$35,110
416,178
kWh
|
- | - | |
05 | 2.2437: Recover waste heat from equipment | $41,306 | $65,900 | - |
$41,306
-
MMBtu
|
- | |
06 | 2.1131: Repair faulty insulation in furnaces, boilers, etc | $946 | $983 | - |
$946
-
MMBtu
|
- | |
07 | 2.2515: Use optimum thickness insulation | $381 | $662 |
$381
4,396
kWh
|
- | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $956 | - |
$1,055
12,603
kWh
|
- | $(-99.0) | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,628 | $1,469 |
$1,628
19,343
kWh
|
- | - | |
10 | 2.7144: Install spectral reflectors / delamp | $4,827 | $7,325 |
$4,277
50,703
kWh
|
- | $550 | |
11 | 2.6232: Install set-back timers | $2,135 | $3,680 |
$1,983
23,447
kWh
|
- | $152 | |
12 | 2.6232: Install set-back timers | $6,228 | $4,600 |
$5,713
67,702
kWh
|
- | $515 | |
13 | 2.6232: Install set-back timers | $2,424 | $200 |
$2,157
25,498
kWh
|
- | $267 | |
14 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $112 | $91 |
$99
1,172
kWh
|
- | $13 | |
15 | 2.7134: Use photocell controls | $629 | $230 |
$539
6,448
kWh
|
- | $90 | |
16 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $518 | $455 |
$420
4,982
kWh
|
- | $98 | |
17 | 2.7261: Install timers and/or thermostats | $3,098 | $300 |
$3,098
36,635
kWh
|
- | - | |
TOTAL RECOMMENDED | $107,787 | $111,327 |
$63,949
757,910
kWh
|
$42,252
-
MMBtu
|
$1,586 | ||
TOTAL IMPLEMENTED | $25,875 | $22,982 |
$23,433
277,547
kWh
|
$946
-
MMBtu
|
$1,496 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs