Assessment Year 2002
Principal Product Plastic Film Products
NAICS
n/a
SIC 3082: Unsupported Plastics Profile Shapes
Sales Range $10
M
to 50
M
# of Employees 100
Plant Area 225,000
ft2
Annual Production 18,000,000
lb
Production Hrs. Annual 8,760
hrs
Location (State) Minnesota

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $289,988 10,044,960
kWh
Electricity Demand $149,206 21,552
kW-mo/yr
Natural Gas $77,410 18,054
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $35,519 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $10,685

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
01 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $2,847 $866 $2,015
69,960
kWh
$832
-
kW-mo/yr
-
02 2.4221: Install compressor air intakes in coolest locations $1,497 $100 $1,019
35,391
kWh
$478
-
kW-mo/yr
-
03 2.4231: Reduce the pressure of compressed air to the minimum required $114 $17 $48
1,664
kWh
$66
-
kW-mo/yr
-
04 2.4239: Eliminate or reduce compressed air usage $532 $400 $532
18,467
kWh
- -
05 2.2437: Recover waste heat from equipment $975 $1,200 - - $975
-
MMBtu
06 2.7142: Utilize higher efficiency lamps and/or ballasts $7,617 - $5,739
199,278
kWh
$1,878
-
kW-mo/yr
-
07 2.7135: Install occupancy sensors $309 $600 $309
10,746
kWh
- -
08 2.7142: Utilize higher efficiency lamps and/or ballasts $6,112 $11,834 $4,085
141,832
kWh
$2,027
-
kW-mo/yr
-
09 2.4133: Use most efficient type of electric motors $1,426 - $1,072
37,232
kWh
$354
-
kW-mo/yr
-
10 2.6232: Install set-back timers $101 $197 $101
3,494
kWh
- -
11 2.2614: Use cooling tower or economizer to replace chiller cooling $13,904 $4,000 $11,208
389,169
kWh
$2,696
-
kW-mo/yr
-
12 2.2511: Insulate bare equipment $85 $180 $85
2,957
kWh
- -
TOTAL RECOMMENDED $35,519 $19,394 $26,213
910,190
kWh
$8,331
-
kW-mo/yr
$975
-
MMBtu
TOTAL IMPLEMENTED $10,685 $13,094 $7,406
257,139
kWh
$3,279
-
kW-mo/yr
-
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs