| Assessment Year | 1993 |
|---|---|
| Principal Product | TECH CERAMIC MATERIAL |
| NAICS |
n/a
|
| SIC | 3264: Porcelain Electrical Supplies |
| Sales Range | $1 M to 5M |
| # of Employees | 32 |
| Plant Area |
n/a
|
| Annual Production | 37,000
lb
|
| Production Hrs. Annual | 6,000
hrs
|
| Location (State) | California |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $215,059 | 2,211,020 |
kWh
|
$0.097 |
| Natural Gas | $346 | 38 |
MMBtu
|
$9.11 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $9,566 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $6,254 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4133: Use most efficient type of electric motors | $720 | $470 |
$720
7,620
kWh
|
- | - | |
| 02 | 2.7261: Install timers and/or thermostats | $1,902 | $300 |
$1,583
16,413
kWh
|
$319
-
MMBtu
|
- | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $815 | - |
$902
8,499
kWh
|
- | $(-87.0) | |
| 04 | 2.7144: Install spectral reflectors / delamp | $1,500 | $2,520 |
$1,314
13,482
kWh
|
- | $186 | |
| 05 | 2.6232: Install set-back timers | $1,317 | $2,120 |
$1,144
11,723
kWh
|
- | $173 | |
| 06 | 2.2491: Use cooling air which cools hot work pieces for space heating | $3,312 | $11,632 |
$3,312
34,291
kWh
|
- | - | |
| TOTAL RECOMMENDED | $9,566 | $17,042 |
$8,975
92,028
kWh
|
$319
-
MMBtu
|
$272 | ||
| TOTAL IMPLEMENTED | $6,254 | $5,410 |
$5,663
57,737
kWh
|
$319
-
MMBtu
|
$272 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs