| Assessment Year | 1991 |
|---|---|
| Principal Product | SOFT DRINKS |
| NAICS |
n/a
|
| SIC | 2086: Bottled and Canned Soft Drinks and Carbonated Waters |
| Sales Range | $10 M to 50M |
| # of Employees | 125 |
| Plant Area |
n/a
|
| Annual Production | 12,000,000
pieces
|
| Production Hrs. Annual | 8,060
hrs
|
| Location (State) | Pennsylvania |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $245,290 | 3,402,403 |
kWh
|
$0.072 |
| Natural Gas | $163,283 | 43,940 |
MMBtu
|
$3.72 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $15,010 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $15,010 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,047 | - |
$1,047
14,361
kWh
|
- | |
| 02 | 2.4221: Install compressor air intakes in coolest locations | $2,995 | $257 |
$2,995
41,325
kWh
|
- | |
| 03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $291 | $140 |
$291
4,103
kWh
|
- | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,732 | $443 |
$3,732
51,583
kWh
|
- | |
| 05 | 2.2511: Insulate bare equipment | $5,106 | $883 | - |
$5,106
-
MMBtu
|
|
| 06 | 2.1233: Analyze flue gas for proper air/fuel ratio | $1,839 | $500 | - |
$1,839
-
MMBtu
|
|
| TOTAL RECOMMENDED | $15,010 | $2,223 |
$8,065
111,372
kWh
|
$6,945
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $15,010 | $2,223 |
$8,065
111,372
kWh
|
$6,945
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs