| Assessment Year | 1991 |
|---|---|
| Principal Product | AEROSPACE FASTENERS |
| NAICS |
n/a
|
| SIC | 3452: Bolts, Nuts, Screws, Rivets, and Washers |
| Sales Range | $10 M to 50M |
| # of Employees | 135 |
| Plant Area |
n/a
|
| Annual Production | 12,000,000
pieces
|
| Production Hrs. Annual | 4,732
hrs
|
| Location (State) | New Jersey |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $561,171 | 7,080,891 |
kWh
|
$0.079 |
| Natural Gas | $96,838 | 17,708 |
MMBtu
|
$5.47 |
| Fuel Oil #4 | $115,249 | 24,124 |
MMBtu
|
$4.78 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $54,553 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $54,553 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Fuel Oil #4 Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $3,496 | - |
$3,496
44,256
kWh
|
- | - | |
| 02 | 2.4221: Install compressor air intakes in coolest locations | $1,138 | $330 |
$1,138
14,361
kWh
|
- | - | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $7,196 | $1,735 |
$7,196
91,149
kWh
|
- | - | |
| 04 | 2.2514: Cover open tanks | $506 | $1,164 | - |
$506
-
MMBtu
|
- | |
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,454 | - |
$2,454
31,067
kWh
|
- | - | |
| 06 | 2.2614: Use cooling tower or economizer to replace chiller cooling | $17,916 | $11,500 |
$17,916
226,846
kWh
|
- | - | |
| 07 | 2.1233: Analyze flue gas for proper air/fuel ratio | $8,091 | $500 | - | - |
$8,091
-
MMBtu
|
|
| 08 | 2.2414: Use waste heat from hot flue gases to preheat | $13,756 | $6,800 | - | - |
$13,756
-
MMBtu
|
|
| TOTAL RECOMMENDED | $54,553 | $22,029 |
$32,200
407,679
kWh
|
$506
-
MMBtu
|
$21,847
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $54,553 | $22,029 |
$32,200
407,679
kWh
|
$506
-
MMBtu
|
$21,847
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Fuel Oil #4 Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs