| Assessment Year | 2005 |
|---|---|
| Principal Product | Potato and corn chips |
| NAICS | 311919: Other Snack Food Manufacturing |
| SIC | 2096: Potato Chips, Corn Chips, and Similar Snacks |
| Sales Range | $50 M to 100M |
| # of Employees | 300 |
| Plant Area |
300,000
ft2
|
| Annual Production | 18,000,000
pieces
|
| Production Hrs. Annual | 7,488
hrs
|
| Location (State) | Washington |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $715,158 | 17,008,350 |
kWh
|
$0.042 |
| Electricity Demand | $181,519 | 390,348 |
kW-mo/yr
|
$0.47 |
| Electricity Fees | $2,088 | - |
|
- |
| Natural Gas | $1,000,000 | 357,286 |
MMBtu
|
$2.80 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $67,670 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $25,000 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.4224: Upgrade controls on compressors | $32,471 | - |
$27,022
643,131
kWh
|
$5,449
-
kW-mo/yr
|
- | - | |
| 02 | 2.6232: Install set-back timers | $2,880 | $300 |
$2,880
72,000
kWh
|
- | - | - | |
| 03 | 4.111: Add equipment/ operators to reduce production bottleneck | $25,000 | $26,000 | - | - | - | $25,000 | |
| 04 | 2.3212: Optimize plant power factor | $7,319 | $8,000 | - | - | $7,319 | - | |
| TOTAL RECOMMENDED | $67,670 | $34,300 |
$29,902
715,131
kWh
|
$5,449
-
kW-mo/yr
|
$7,319 | $25,000 | ||
| TOTAL IMPLEMENTED | $25,000 | $26,000 | - | - | - | $25,000 | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs