| Assessment Year | 2023 |
|---|---|
| Principal Product | polyethylene film |
| NAICS | 326199: All Other Plastics Product Manufacturing |
| SIC | 3089: Plastics Products, Not Elsewhere Classified |
| Sales Range | $50 M to 100M |
| # of Employees | 250 |
| Plant Area |
195,000
ft2
|
| Annual Production | 15,000,000
lb
|
| Production Hrs. Annual | 8,736
hrs
|
| Location (State) | Arkansas |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $1,331,399 | 20,464,400 |
kWh
|
$0.065 | |
| Electricity Demand | $434,755 | 39,373 |
kW-mo/yr
|
$11.04 | |
| Natural Gas | $346,779 | 42,536 |
MMBtu
|
$8.15 | |
| Waste Disposal Costs | |||||
| Water Usage | $16,016 | 4,139 |
Tgal
|
$3.87 | |
| Water Disposal | $21,373 | 4,139 |
Tgal
|
$5.16 | |
| TOTAL YEARLY COSTS | $2,150,322 | ||||
| RECOMMENDED SAVINGS* | $139,150 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | $31,380 | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4221: Install compressor air intakes in coolest locations | $2,672 | $2,688 |
$2,672
41,122
kWh
|
- | - | |
| 02 | 2.7232: Replace existing hvac unit with high efficiency model | $3,917 | $22,000 |
$3,917
60,264
kWh
|
- | - | |
| 03 | 2.7261: Install timers and/or thermostats | $573 | $870 |
$369
5,669
kWh
|
- |
$204
-
MMBtu
|
|
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $26,890 | $94,115 |
$21,441
329,865
kWh
|
$5,449
-
kW-mo/yr
|
- | |
| 05 | 2.9114: Use solar heat to make electricty | $93,859 | $858,000 |
$93,859
1,443,987
kWh
|
- | - | |
| 06 | 2.2414: Use waste heat from hot flue gases to preheat | $11,239 | $12,700 | - | - |
$11,239
-
MMBtu
|
|
| TOTAL RECOMMENDED | $139,150 | $990,373 |
$122,258
1,880,907
kWh
|
$5,449
-
kW-mo/yr
|
$11,443
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $31,380 | $116,985 |
$25,727
395,798
kWh
|
$5,449
-
kW-mo/yr
|
$204
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs